Digital Monitoring Products Inc PC0096 Manual Do Utilizador

Página de 27
Digital Monitoring Products
 
XT30/XT50 Installation Guide
8
InstallatIon
6.7  XT30/XT50 Standby Battery Calculations
Standby Battery Power Calculations
Alarm Current
XT30 Panel
XT50 Panel
     Built-in Network (additional current)
     Built-in Cellular (additional current) 
Active Zones 1-9  
Active Zone 10  
2-Wire Smoke Detectors 
Panel Bell Output
x
x
x
x
x
x
125mA
145mA
145mA
17mA
1.6mA
4mA
0.1mA
______mA
______
______
______
______
______
______
Qty ______
Qty ______
Qty ______
1500mA 
x
x
x
x
125mA
145mA
145mA
65mA
*2mA
30mA
0.1mA
Max.
______mA
______
______
______
______
______
______
______
263G Digital Cellular Communicator
x
17mA ______
Qty ______
x
65mA ______
1100D Wireless Receiver
x
40mA ______
Qty ______
x
40mA ______
1100DH Wireless High Power Receiver
x 160mA ______
Qty ______
160mA ______
1100DI Wireless In-Line Receiver
x
30mA ______
Qty ______
30mA ______
690 Security Command Keypad
x
77mA  ______
Qty ______
x
84mA ______
693 Security Command Keypad
x
92mA ______
Qty ______
x
120mA ______
790 Security Command Keypad 
Active Zones (EOL Installed)
x
77mA
1.6mA
______
______
Qty ______
Qty ______
x
x
84mA
*2mA
______
______
793 Security Command Keypad 
Active Zones (EOL Installed)
x
92mA
1.6mA
______
______
Qty ______
Qty ______
x
x
120mA
*2mA
______
______
7060/7160 Thinline/7060A Aqualite Keypad
x
72mA ______
Qty ______
x
87mA ______
7063/7163 Thinline/7063A Aqualite Keypad
x
85mA ______
Qty ______
x
100mA ______
7360 Thinline Icon Keypad
7363 Thinline Icon Keypad
7070/7170 Thinline/7070A Aqualite Keypad 
Active Zones (EOL Installed)
x
x
x
60mA
73mA
72mA
1.6mA
______
______
______
______
Qty ______
Qty ______
Qty ______
Qty ______
x
x
x
x
67mA
80mA
87mA
*2mA
______
______
______
______
7073/7173 Thinline/7073A Aqualite Keypad 
Active Zones (EOL Installed)
x
85mA
1.6mA
______
______
Qty ______
Qty ______
x
x
100mA
*2mA
______
______
734 Wiegand Interface Module 
Active Zones (EOL Installed)
x
x
15mA
1.6mA
______
______
Qty ______
Qty ______
x
x
15mA
*2mA
______
______
738A Ademco Wireless Interface Module
x
75mA ______
Qty ______
x
75mA ______
708 Bus Extender Module (one pair)
x
20mA ______
Qty ______
x
20mA ______
710 Bus Splitter/Repeater Module
x
30mA ______
Qty ______
x
30mA ______
714 Zone Expansion Modules 
Active Zones (EOL Installed)
x
x
7mA
1.6mA
______
______
Qty ______
Qty ______
x
x
7mA
*2mA
______
______
712-8 Zone Expansion Module 
Active Zones (EOL Installed)
x
x
17mA
1.6mA
______
______
Qty ______
Qty ______
x
x
17mA
*2mA
______
______
714-8, 714-16 Zone Expansion Module 
Active Zones (EOL Installed)
x
x
20mA
1.6mA
______
______
Qty ______
Qty ______
x
x
20mA
*2mA
______
______
715 Zone Expansion Module 
Active Zones (EOL Installed) 
2-Wire Smokes
x
x
x
7mA
4mA
.1mA
______
______
______
Qty ______
Qty ______
Qty ______
x
x
x
7mA
*30mA
.1mA
______
______
______
715-8, 715-16 Zone Expansion Modules 
Active Zones (EOL Installed) 
2-Wire Smokes
x
20mA
4mA
.1mA
______
______
______
Qty ______
x
20mA
*30mA
.1mA
______
______
______
Aux. Powered Devices on Terminals 7 and 11 
Other than Keypads and Modules
______mA
______mA
Total Standby 
Total Standby______mA x number of Standby Hours 
needed 
Total Alarm
  
* Based on 10% of active zones in alarm condition.
______mA
______ =
______mA 
+
Total
Total Alarm
________mA-hours
________mA-hours
________mA-hours
X .001
= ________Amp-hrs 
______mA
Required