Digital Monitoring Products Inc PC0136 Manual Do Utilizador
734W Installation Guide
Digital Monitoring Products
3
Zone Terminals
Terminals 5-11 on J9 connect grounded zones 1 through 3. These zones
have a grounded side and cannot be used for fire-initiating devices. Zones
2 and 3 can also be used for access control with Zone 2 providing a bypass
option and Zone 3 providing Request to Exit functionality. Zone 4 terminals
provide a non-powered Class B, Style A zone. Use the supplied, DMP
Model 311 1K Ohm End-of-Line resistors on each zone. Refer to the panel
programming guide for programming instructions.
Zone #
Recommended Device
Residential Fire Devices?
1
Any burglary device
No
2
Door Contact
No
3
REX (PIR or Button)
No
4
Any device
Yes
Annunciator Header
The 4-pin J26 header located on the far right of the circuit board is used to wire the Armed Status, Remote Annunciation,
and the Remote LED Control. The open collectors will supply a ground for a
maximum current of 50mA @ 30 VDC. Connect a Model 300 4-wire harness to
the 4-pin header for connection of the following indicators:
--AS (Armed Status)
Armed Status provides an unsupervised switched ground for a visual or audible
--AS (Armed Status)
Armed Status provides an unsupervised switched ground for a visual or audible
armed status indicator that turns on when the burglary areas are armed, such
as SYSTEM ON or ALL SYSTEM ON. Connect the wire from the 4-wire harness to
an Armed Status output.
--RA (Remote Annunciation)
Remote Annunciation provides an unsupervised switched ground for a remote
--RA (Remote Annunciation)
Remote Annunciation provides an unsupervised switched ground for a remote
annunciator that turns on when the Model 734W on-board piezo turns on.
Connect the wire from the 4-wire harness to a remote annunciator. The
remote annunciator silences when the RA restores. The remote annunciator (RA) switched ground will operate even if the
speaker is programmed not to operate.
--LC (Remote LED Control)
Remote LED Control provides an unsupervised switched ground for a visual indicator that turns on when the Model 734W
--LC (Remote LED Control)
Remote LED Control provides an unsupervised switched ground for a visual indicator that turns on when the Model 734W
relay activates. Connect the wire from the 4-wire harness to an LED. The LED turns on for the duration the door strike
relay is on. HID readers optionally provide a connection for LED reader control.
Auxiliary Outputs 1 & 2
The 734W controls Auxiliary Outputs 1 and 2 when the Activate Zone 2 Bypass programming option is enabled and the Zone
2 Bypass Time is set. When the door contact (Zone 2) is opened while the door strike is
activated, the Zone 2 Bypass Time starts. If the door has not closed at the end of the timer,
Aux Output 1 is turned on and the timer starts again. If the door is still open at the end of the
second timer, Aux Output 2 is turned on. Aux Outputs 1 and 2 turn off when the door contact
is closed. Use the Model 431 Relay Harness for connection of Output 1 and Output 2 as shown
in Table 1.
Reset Header
The reset header is located just above and to the right of the WiFi network connector (see Figure 1) and is used to reset
the 734W module. To reset the module when first installing the system, install the reset jumper before applying power to
the module. After connecting the power, remove the reset jumper.
To reset the module while the system is operational, for example, prior to reprogramming, install the reset jumper
To reset the module while the system is operational, for example, prior to reprogramming, install the reset jumper
without powering down the system. Remove the reset jumper after one or two seconds.
PROG (Programming)
The 734W module is programmable from a 32-character keypad set to address one. For
12 Volt applications, connect the
keypad to the module using a Model 330 4-wire harness.
For
For
24 Volt applications, connect the keypad to the module using the included WR-0235 4-wire programming harness with
in-line resistor.
Do not connect a keypad using a Model 330 harness if using a 24 volt power supply! Damage to the keypad
could occur.
could occur.
While programming the 734W module with a keypad, advance to the next programming option by pressing the CMD key.
Return to the previous programming option or erase an incorrect entry by pressing the Back Arrow key. Make a selection
by pressing the Select key below the option you wish to select. While in programming mode no 734W communication with
the panel can occur.
Figure 8: 734W Zone Terminals
Remote Audible Annunciator
Armed Status Output
Output 2
Output 1
Remote LED Control
Figure 9: 734W Annunicator Outputs
Form C Relays (J2)
Output Color Code–Model 431 Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Table 1: Harness Wiring