Enlighted Inc. FS-D2 Manual Do Utilizador

Página de 2
Page 1
Cautionary Suggestions
Disconnect all power before installation or service.
Installation and maintenance must be performed by qualified
personnel.
Installations and maintenance must be performed in accordance
with state, local, and national electrical codes and requirements.
Installation Steps
Page 2
Page 3
Fixture Mount
DALI Sensor (D2)
Installation
Instructions
Figure 1: Fixture Mount DALI Sensor
Shipped Components
• DALI Sensor (D2)
Tools You May Need
• Wire cutter and stripper
Supplies You May Need
• 18 AWG Solid Copper Wire, rated >=300V
Step
Description
1
Turn off all power to the light fixture by switching off the circuit
breaker.
2
The face of the sensor is only 1.08 inches (27mm) in diameter and is 
designed to mount in a ½ inch trade size (0.875 inch) hole.. (All parts 
of  the sensor are inside the lighting fixture except for a ring and 
spring.)
3
Determine the location for the sensor in fixture, and either remove 
an existing ½ inch knockout or cut a hole in the fixture.
4
Orient the sensor and measure the length between it and the LED 
driver “DALI connections”, and cut two lengths of 18 AWG wire 
that are at least this length plus 1 inch.
5
Strip each end of the 2 wires leaving 
3
/
8
inch of exposed wire.
6
Insert one end of the wires in the sensor’s wire holes and the other in 
the DALI LED driver “DALI connections” wire holes
7
Remove (by unscrewing) the outer ring from the sensor (saving the 
ring and pressure spring). On the inside of the fixture, insert the 
sensor in the hole in the fixture and on the outside of the fixture, 
replace the spring and screw back on the outer ring. Tighten firmly, 
but do no over tighten.
8
Ready the fixture for use, and when done, restore power to the 
fixture.
<documentID>
Figure 2: Mechanical dimensions of the DALI Sensor
Figure 3: Wiring Diagram
This installation assumes that you have already installed the DALI 
LED driver.