Cautionary Suggestions
•
Installation and maintenance must be performed by
qualified electrician.
•
Installations and maintenance must be performed in
accordance with local, state, and national electrical codes
and requirements.
Problem
Solution
LED is not on when
the device is
powered
1) Check to see that power is present
from the circuit panel.
2) Check the wiring, if LED does not
come on, then replace the
device.
Step Description
J-box Install (see Figure 2)
1
Punch out a ½ inch knock out from the j-box and
insert the threaded end of the plug load controller.
Secure the plug load controller to the j-box with the
supplied locknut.
2
(Main Feed) Feed the j-box with (3) 12 AWG
conductors. (Hot, Neutral, and Ground)
3
Connect the j-box with (4) 12 AWG conductors that
run from the j-box to the receptacle wall box.
(Hot, Switched Hot, Neutral, and Ground)
4
Using wire nuts (or wire connectors):
a) Connect the hot wire from the main feed to the
black wire of the plug load controller.
b) Connect the neutral wire from the main feed to
the white wire of the plug load controller and the
neutral wire that feeds through to the receptacle.
c) Connect the red wire of the plug load controller
to the switched hot wire that feeds through to the
receptacle.
d) Connect the blue wire of the plug load controller
to the hot wire that feeds through to the
receptacle.
e) Connect all ground wires to the j-box.
Receptacle Install (see Figure 4)
5
Break the connection on the “hot side” of the
receptacle between the two outlets.
6
Connect the neutral wire to the neutral connection
on the receptacle.
7
Connect the switched hot wire to the hot side of the
“controlled outlet”.
8
Connect the hot wire to the hot connection of the
“uncontrolled outlet” (always powered).
Installation Steps
Installation Steps (Continued)
Step Description
9
Install the receptacle in the wall box
10
Attach a receptacle faceplate that distinguishes the
controlled outlet.
11
Attach the included MAC address sticker on the
faceplate.
Figure 2: J-box with plug load controller, showing main
feed and wiring to receptacle.
Figure 3: Wiring Diagram
Figure 4: Receptacle wiring
Main feed:
•
Hot
•
Neutral
•
Ground
Receptacle feed:
•
Hot
•
Switched Hot
•
Neutral
•
Ground
Hot
Neutral
Switched
Hot
Ground