Honeywell International Inc. WFSSD Manual Do Utilizador
PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013
23
Operations
FWSG
Factory Default
Factory default is the initial mode of the FWSG. The FWSG and peripheral devices do not provide
any fire protection when they are in factory default mode. The FWSG does not communicate with
wireless devices. The only wireless communication is with the configuration tool. The configura-
tion tool needs to be within 20 feet of the FWSG for communication. The FWSG needs to be
assigned a profile before continuing the installation.
The FWSG reports a ‘PROFILE MISSING' or ‘PR MIS’ trouble to the FACP. The FWSG reports
The FWSG reports a ‘PROFILE MISSING' or ‘PR MIS’ trouble to the FACP. The FWSG reports
“Factory Default” to the communicator display of the PC Tools application.
Profile Configured
The FWSG enters the profile configured mode after getting assigned a profile from the tool or a
distributor or creating a profile. Profile configured mode is a temporary mode before the FWSG
transitions to mesh formation or normal mode.
The FWSG does not provide fire protection in the profile configured mode. While in the profile
The FWSG does not provide fire protection in the profile configured mode. While in the profile
configured mode, the FWSG reports a "MESH NOT FORMED" or "NO MSH" trouble to the
FACP. The FWSG reports “Profile Assigned” to the communicator display of the PC Tools appli-
cation.
Mesh Formation
The FWSG must have a profile before entering mesh formation. The FWSG and the peripheral
devices do not provide any fire protection in mesh formation. The FWSG automatically enters
mesh formation mode in the following ways:
• After creating a profile using the mesh formation sensor.
• After activating the mesh formation sensor with a magnet when the FWSG contains a
• After activating the mesh formation sensor with a magnet when the FWSG contains a
profile.
• Automatically after startup when the FWSG previously was part of a mesh.
• By command from the PC Tools application.
• By command from the FACP.
• By command from the PC Tools application.
• By command from the FACP.
A FWSG in mesh formation mode instructs all devices in the mesh to also transition to mesh for-
mation. The FWSG and all communicating devices search for new or lost devices with the same
profile to join the network.
If the FWSG automatically entered mesh formation mode after startup, then mesh formation termi-
If the FWSG automatically entered mesh formation mode after startup, then mesh formation termi-
nates after all existing devices are recovered. If new devices are found or if mesh formation was
initiated by the user, then mesh formation terminates after a period of 10 minutes without any new
devices joining the mesh. At any point, mesh formation can be terminated by user interaction by
activating the magnet sensor again, by using the PC Tools application, or by using FACP.
The FWSG reports a “NO WIRELESS DEVS” or “NO DEV” trouble when it is in Mesh Formation
The FWSG reports a “NO WIRELESS DEVS” or “NO DEV” trouble when it is in Mesh Formation
mode without any attached devices. The FWSG reports a “MESH IS FORMING” or “MS FRM”
trouble when it is mesh formation mode with additional devices in the mesh. The FWSG reports
“Mesh Formation” to the communicator display of the PC Tools application.
Initial Mesh Optimization
The initial mesh optimization mode automatically runs after each mesh formation. The FWSG and
peripheral devices do not provide fire protection during the initial mesh optimization. Mesh opti-
mization mode analyzes the signal strengths between devices. The FWSG designates the primary
and secondary communication paths between devices that provide a redundant path for all trans-
missions. Mesh optimization terminates automatically once all devices have a redundant communi-
cation path and signal strengths that meet the requirements of primary and secondary transmission
paths. Any device that does not have a redundant path or meet the requirements for signal strength
will report a fault.