Operations
Factory Default Mode
Factory default mode is the initial mode of the gateway. In this mode, the gateway and peripheral devices do not provide any fire protec-
tion. The gateway does not communicate with wireless detectors or modules in factory default mode. The only wireless communication 
in factory default mode is between the gateway and SWIFT Tools. SWIFT Tools must be within 20 feet of the gateway for proper com-
munication. The gateway must be assigned a profile before continuing configuration.
The gateway reports a “NO PROFILE” trouble to the FACP. The gateway reports “Factory Default” to the communicator display of 
SWIFT Tools.
Transitions back to Factory Default mode are not shown in the above diagram. However, any time the profile is removed from the gate-
way, it will return to Factory Default mode.
Profile Configured
The gateway enters the profile configured mode once a profile is assigned by SWIFT Tools or a distributor; or after creating a profile 
using the magnetic sensor. Profile configured mode is a temporary mode before the gateway transitions to mesh formation or normal 
mode. 
The gateway does not provide fire protection in the profile configured mode. While in the profile configured mode, the gateway reports 
a “RF MESH NOT FORMED” or “RF MESH” trouble to the FACP. The gateway reports “Profile Assigned” to the communicator dis-
play of the SWIFT Tools application.
Mesh Formation
The gateway must have a profile before entering mesh formation mode. The gateway and the peripheral devices do not provide any fire 
protection in this mode. The gateway enters mesh formation mode:
after creating a profile using the mesh formation sensor.
after activating the mesh formation sensor with a magnet when the gateway contains a profile.
automatically after start-up when the gateway was previously part of a mesh.
by a command from the SWIFT Tools application.
A gateway in mesh formation mode instructs all devices in the mesh to also transition to mesh formation mode. The gateway and all 
communicating devices search for new or lost devices with the same profile to join the network.
If the gateway automatically entered mesh formation after start-up, mesh formation will terminate 10 minutes after the last device has 
joined or after all existing devices are recovered. If new devices are found or if mesh formation was initiated by the user, then mesh for-
mation terminates after a period of 10 minutes without any new devices joining the mesh. At any point Mesh formation can be termi-
nated by user interaction by activating the magnet sensor again or by using the SWIFT Tools application.
The gateway reports a “RF MESH FORMING” or “RF MESH” trouble when it is mesh formation mode with additional devices in the 
mesh. The gateway reports “Mesh Formation” to the communicator display of the SWIFT Tools application.
Initial Mesh Restructuring Mode
Initial mesh restructuring mode automatically runs after each mesh formation. The gateway and peripheral devices do not provide fire 
protection during the initial mesh restructuring mode. Mesh restructuring analyzes signal strengths between devices. The gateway desig-
nates the primary and secondary communication paths between devices that provide a redundant path for all transmissions. Mesh 
restructuring automatically terminates once all devices have a redundant communication path and signal strengths that meet the require-
ments of primary and secondary transmission paths. Any device that does not have a redundant path or meet the requirements for signal 
strength will report a fault.
The gateway reports a “RF MESH FORMING” or “RF MESH” trouble to the FACP. The gateway reports “Restructuring” to the com-
municator display of the SWIFT Tools application.
Normal Mode
Normal mode is the network’s standard operating state. The mesh network has been formed and is providing fire protection. The mesh 
network will continuously search for additional devices with a matching profile to join the mesh. To avoid interference, the mesh net-
work periodically checks for adjacent mesh networks created by Honeywell. The gateway reports “Normal” to the communicator display 
of the SWIFT Tools application.
Rescue Mode
During normal mode, if an out-of-network device with a matching profile is discovered by the network, the gateway will trigger rescue 
mode in all communicating devices. All devices in communication continue to provide fire protection during rescue mode but also 
search for a lost or added device. Rescue mode automatically terminates 3 minutes after the last device is rescued and returns to normal 
mode. The gateway does not report troubles during rescue mode but reports “Rescue” to the communicator display of the SWIFT Tools 
application.
Mesh Restructuring Mode
In addition to the initial mesh restructuring mode, mesh restructuring is automatically performed after any restoration of communication 
to a device or to recover from a link failure (Class A fault). Mesh restructuring that occurs during normal mode does not generate a trou-
ble message. During mesh restructuring, fire protection is provided by all devices that are participating in the mesh communication. The 