CleanAlert LLC FS-242 Manual Do Utilizador

Página de 14
 
 
8
 
unplugging the optional AC Adapter, or in the case of conduit-powered 
models (“C”) contacting your HVAC system electrician to have the power 
to the Monitor cut. Wait for a minute and restore power.  If your 
FILTERSCAN
®
 unit is operating with both AC Adapter and batteries 
installed, both will need to be removed in order to reset the malfunction. If 
this does not reset the malfunction alarm, contact the company that you 
purchased the 
FILTERSCAN
®
 from for repair information. 
 
Calibrating When
  
Whenever a new air filter is installed, the 
FILTERSCAN
®
 clog detector 
Installing a New Air Filter
  system must be calibrated. Calibration establishes the clogged air filter 
detection threshold based upon the condition recorded for a new air filter.  
When a new air filter is installed, its condition is recorded and saved in 
nonvolatile memory.  
 
1.  Insure that the HVAC system is OFF at the thermostat. 
2.  Remove the dirty air filter from the HVAC system. 
3.  Install a new, clean air filter into the HVAC system. 
4.  Make sure the 
FILTERSCAN
®
 Monitor power is ON via either AC 
Adapter or Battery installation, making sure the low battery indication 
is not being displayed. 
5.  Depress the ZERO/CLEAN button on the 
FILTERSCAN
®
 Monitor. 
6.  Wait for the red STATUS LED to illuminate. 
7.  Depress the ZERO/CLEAN button again. 
8.  Wait several seconds for the STATUS LED to change from blinking 
yellow to blinking green. 
9.  Turn the HVAC system ON at the system thermostat. 
10.  Set the thermostat temperature adjustment to either increase or 
decrease the room temperature by four degrees, which should be 
enough to signal the HVAC system to turn heating or cooling on. 
11.  Wait one minute for the HVAC system blower fan to turn on and 
stabilize. 
12.  Depress the ZERO/CLEAN button again. 
13.  Wait several minutes for the STATUS LED to turn from blinking yellow 
to blinking green. During this time, the unit is recording the condition 
of a clean air filter. 
14.  Wait several seconds for the blinking green STATUS LED to turn 
OFF. 
15.  Return the thermostat to normal operating temperature. 
 
Your 
FILTERSCAN
®
 Monitor is now calibrated to the type of air filter you 
have installed. Depending on the air filter type and manufacturing 
tolerances, you may need to calibrate the 
FILTERSCAN
®
 air filter 
clogging detector each time a new air filter is installed. 
 
Automatic Adjustment  
ATTENTION - HVAC systems with two-speed blowers!  Typical HVAC 
systems will have different blower speeds for Heat and A/C.  The 
FILTERSCAN
®
 Monitor automatically adapts to the changes in HVAC 
blower speeds. 
 
 
S
pecifications 
 
Pressure Differential Range 
0.1 to 4.0 in H
2
Clog Filter Trigger Point 
1.5 to 2 times initial differential pressure (at the recommended setting 
on the SERVICE FILTER control) 