Napco Security Systems Inc GEMCWLSMK Manual Do Utilizador

Página de 4
 
The GEMC-WL-SMK is a high-quality photoelectric smoke 
detector with built-in supervised digitally-coded radio trans-
mitter.  It is compatible with Napco's GEM-RECV and 
GEMC-RECV Series supervised receivers that monitor 
alarms, restores, low battery, tamper and status.   
 
During normal operation, when unit is in standby mode and 
is within proper sensitivity limits, the green LED on the 
GEMC-WL-SMK flashes once every 10 seconds.  As soon 
as smoke is detected, the GEMC-WL-SMK sounds a local 
alarm and the transmitter sends an alarm signal to the su-
pervised receiver (Operating Frequency:  319.5Mhz).  The 
alarm signal is repeated every 10 seconds thereafter as 
long as smoke is still present.  A restore report is sent when 
the smoke detection chamber clears.  Supervisory status 
reports are sent from the GEMC-WL-SMK every hour. 
 
Note:   Coding switches are not required or used in the 
GEMC-WL-SMK; each transmitter is assigned a unique 
identification code number at the factory. 
R
333 Bayview Avenue 
Amityville, New York 11701 
For Sales and Repairs, (800) 645-9445 
For Technical Service, (800) 645-9440 
Publicly traded on NASDAQ   Symbol: NSSC 
© NAPCO 2010 
GEMC-WL-SMK 
SUPERVISED 
WIRELESS DIGITAL SMOKE DETECTOR 
INSTALLATION INSTRUCTIONS 
WI1726A.03  01/10 
Low Battery Warning 
The smoke detector and transmitter are powered by 
one 3-volt lithium battery (supplied) that can power the 
unit for at least one year.  If battery voltage drops below 
normal, a low battery report is sent to the panel for a 
period of 48 hours; if the voltage is still below normal 
after this time, the detector sounder will chirp and its red 
LED will flash every 45 seconds.  Note:  Unit shuts down 
after 7 days.  A low-battery report is sent to the receiver 
with any status or alarm transmission.  If a low-battery 
condition is indicated, always replace battery.   
NOTE:  Temperature and humidity extremes may re-
duce the life of the battery.  In addition, the GEMC-WL-
SMK detector is designed to prevent re-mounting to the 
mounting plate without the battery installed. 
Use Only Battery Specified In Marking.  Use of A Differ-
ent Battery May Have A Detrimental Effect On Detector 
Operation. 
Remove the mounting plate.  Remove the 
GEMC-WL-SMK mounting plate by turning the 
plate counter-clockwise and pulling it up. 
Identify components.  Examine the GEMC-
WL-SMK to identify the component locations. 
Install battery. Place one 3-volt lithium Duracell 
DL123A, Varta CR123A, Panasonic CR123A or 
Sanyo CR123A in its battery compartment, ob-
serving correct polarity.  Install battery and enroll the 
GEMC-WL-SMK into the control panel before mount-
ing.  During power up and status initialization, both the 
green and red LED's blink four times in unison.  Then 
press the TEST button once to complete installation. 
continued 
 
 
 
LIFT TO  
REMOVE 
MOUNTING 
PLATE 
TWIST 
MOUNTING 
PLATE TO 
UNLOCK 
ENSURES UNIT 
IS CORRECTLY 
MOUNTED 
RF ID# 
LABEL 
BATTERY  
COMPARTMENT 
3-VOLT BATTERY  
LOCATION 
(–) 
(+)