Troubleshooting
LED codes
Pump LED sequence code
Explanation
No light
Pump is off — no power
Steady light on LED
Pump is running or on stand-by
One short and one long flash
Low input voltage to pump
Two short and one long flash
Communication is lost between pump and valve
Three short and one long flash
Pump is overheated
Four short and one long flash
Pump is overloaded
Five short and one long flash
Blocked rotor inside pump
Six short and one long flash
Low battery voltage at the valve
Short fast flashes
Pump is in pairing mode
Repeater / push-button LED sequence code
Explanation
Steady light
System is running
Seldom flashes
System is running
Short fast flashes
Push-button / signal repeater is in pairing mode
Operation troubleshooting
Symptom
Cause
Remedy
Pump does not turn on
Timer slide switch is set to “OFF”
position or timer clock is not
programmed to allow operation.
Set the slide switch to the “ON”
position or program the timer
clock.
Water at the valve is already at
the set temperature and does not
require pump operation.
Pump will turn on when the
water at the valve cools. Verify
the temperature setting on the
pump.
Outlet has no power
Check that there is power at the
outlet. Make sure the outlet that
the pump is plugged into is not
controlled by a wall switch.
GFCI is tripped.
Verify the “TEST” and “RESET” of
the GFCI outlet that the pump is
plugged into.