Eaton T2235-AB-NFBC20 Manual Do Utilizador
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
Option 5
09S = 9’ cable with straight blade plug
09L = 9’ cable with locking plug
15S = 15’ cable with straight blade plug
15L = 15’ cable with locking plug
C20 = IEC C20 power inlet, cables ordered
separately, AB version only
09S = 9’ cable with straight blade plug
09L = 9’ cable with locking plug
15S = 15’ cable with straight blade plug
15L = 15’ cable with locking plug
C20 = IEC C20 power inlet, cables ordered
separately, AB version only
Option 1
A1 = 120V/15A input, 12A output
Receptacles: (8) NEMA 5-15R
A2 = 120V/20A input, 16A output
Receptacles: (8) NEMA 5-20R
AB = 100-240V/20A input, 16A output
Output: (8) IEC C13 (1) IEC C19
C1 = 120V/30A input, 24A output
Receptacles: (8) NEMA 5-15R
C2 = 120V/30A input, 24A output
Receptacles: (8) NEMA 5-20R
F3 = 200-240V/30A input, 24A output
Output: (12) IEC C13
F4 = 200-240V/30A input, 24A output
Output: (4) IEC C13 (2) IEC C19
A1 = 120V/15A input, 12A output
Receptacles: (8) NEMA 5-15R
A2 = 120V/20A input, 16A output
Receptacles: (8) NEMA 5-20R
AB = 100-240V/20A input, 16A output
Output: (8) IEC C13 (1) IEC C19
C1 = 120V/30A input, 24A output
Receptacles: (8) NEMA 5-15R
C2 = 120V/30A input, 24A output
Receptacles: (8) NEMA 5-20R
F3 = 200-240V/30A input, 24A output
Output: (12) IEC C13
F4 = 200-240V/30A input, 24A output
Output: (4) IEC C13 (2) IEC C19
Option 3
F = Filtering
N = No Filtering
F = Filtering
N = No Filtering
Option 2
C = Circuit Breaker
N = No Circuit Breaker
C = Circuit Breaker
N = No Circuit Breaker
T 2 2 3 5 -
-
T2235 “Design Your Own” part number guide
PHYSICAL
•
Height 1.72” (1U) x Depth 7.0”
Depth 9.5” - Versions C2, F3, F4
Depth 9.5” - Versions C2, F3, F4
•
Powder coated black steel
•
Detachable mounting brackets allow for
several mounting options
several mounting options
DUAL POWER INPUT
•
Power cables with plugs are attached to
unit through the rear panel cable grip
unit through the rear panel cable grip
•
-AB version has C20 inlets
• Cables must be ordered separately
• Cables must be ordered separately
OVERLOAD CIRCUIT PROTECTION
•
(Optional) Electromagnetic circuit
breakers with long time delay curve
•
Circuit breaker trip guards are provided
•
C1, C2, F3, F4 require circuit breakers
for branch circuit protection to meet
for branch circuit protection to meet
NEC and UL requirements
INDICATOR LIGHTS
•
(5) LED Indicator lights:
•
Main Power, Primary Available,
Secondary Available, Primary Output,
Secondary Output
Secondary Output
POWER OUTLETS
•
North American versions have NEMA
style receptacles, (8) on the rear
style receptacles, (8) on the rear
•
International versions have IEC style
receptacles, (6-12) on the rear
receptacles, (6-12) on the rear
•
Optional cable restraint system with
cable management.
POWER FILTERING (Optional)
•
High performance EMI/RFI filtering
provides protection from both
electromagnetic and radio
frequency interference
electromagnetic and radio
frequency interference
•
Filtering is both Common Mode
(Line to Ground) and Differential
Mode (Line to Line)
(Line to Ground) and Differential
Mode (Line to Line)
SPIKE/SURGE SUPPRESSION (TVSS)
•
Transient voltage surge suppression
prevents damage due to voltage
fluctuations
•
Metal Oxide Varistors (MOVs) are
utilized Line to Line (or neutral)
AUTO TRANSFER SWITCH
•
Firm drop out points allow a transfer before
an under-voltage will affect equipment
operation
an under-voltage will affect equipment
operation
•
Transfer ranges (Voltage):
•
Sources do NOT need to be phase
synchronized
•
Source transfer time of less than 30ms
(clean sine wave to clean sine wave)
(clean sine wave to clean sine wave)
•
Front panel LED’s indicate which sources
are available and selected at the output
are available and selected at the output
VOLTAGE RANGE SELECTION
•
The “AB” International (IEC) version
allows for all three voltage ranges 120V,
208V, or 240V
208V, or 240V
•
Front panel switch to set the drop out
and pull in range to the desired
and pull in range to the desired
voltages see chart above
•
This allows this one version to be
specified for worldwide usage
T2235-AB Front
A2 - Version Back
AB - Version Back
Switches out of Phase Power sources. Optional power Filtering and Circuit Breaker
Nominal
Drop Out
Pull In
120V
90V
103V
208V
182V
195V
240V
197V
210V
AB - Version
ONLY
B
Option 4
B = Color Black - Adjustable Mounting
B = Color Black - Adjustable Mounting