X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Appendix 2 – Load LVD (special order)
This appendix replaces section 7 on page 10 of this manual
L
N
L
N
L
N
BATTERY
LOAD
BREAKERS
RETURN
RECTIFIER
#1
RECTIFIER
#2
SPARE
SLOT
REMOTE ACCESS
CONTROLLER
I²C
LVD
ALARMS
&
SENSORS
NETWORK
COMMUNICATIONS
BATTERY
CURRENT
SHUNT
RECTIFIER
CURRENT
SHUNT
2.5A
5A
5A
10A
25A
85-264VAC is supplied directly to each of the rectifiers which produce a nominal +12VDC 
output.
B  Following a current shunt to measure the rectifier current, the rectifier DC output is fed 
to the battery terminals via a current battery current shunt and a 100A circuit breaker.
C
  The rectifier DC output is also fed to the loads via the LVD (Low Voltage Disconnect, 
and 5 circuit breakers.
D
  The management unit monitors and controls the rectifiers via an I²C interface and also 
checks the status of the DC load and battery breakers.
E  The management unit monitors external sensors and provides alarms.
This unit incorporates an external temperature shutdown feature which is enabled on 
the controller site installation web page (see section 13.4).
  If the temperature at the external temperature sense point goes below -10°C or above 
+65°C a shutdown sequence is initiated.  Once the external temperature returns to 
within these limits the system initiates an automatic restart sequence.