X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
6.0 GENERAL SPECIFICATIONS
6.1 Inputs
Supply Voltage:
85-264VAC Single Phase
Each rectifier position is supplied via an individual
IEC60320 C14 Inlet Socket.
A 3-phase supply may be connected provided that the voltage presented to each
individual rectifier position does not exceed 264VAC.
Supply Current:
Max 9A input @ 85-264VAC per inlet socket.
Battery Input:
Direct connection to DC output bus or via protection
breakers.
Digital alarm inputs:
Volts free contact input*
*Volts free contacts are internally pulled up to 5V with reference to rectifier negative
sense, these lines should not be tied to anything other than volts free contacts or
floating opto-coupler outputs.
Temperature probes:
Sensor with output current proportional to temperature.
6.2 Outputs
Pluggable Breakers:
Up to 5 circuits, 30A max. per circuit.
GMT Fuses:
10 circuits, 12A max. per circuit.
Alarm Relay Contacts:
Form C, 1A max at 30VDC.
Ethernet:
10/100 Base T
6.3 Protection
Supply Input:
Each rectifier is individual fused internally.
Battery:
100A Magnetic Circuit Breaker.
Output Distribution:
According to installed circuit breakers or fuses.
Bulk DC Bus:
Rectifier Current Limiting / Battery Breaker.