SALUS North America Inc. SC102ZB Manual Do Utilizador

Página de 2
For other language versions, please visit www.salusinc.com 
2. Turn Off Power to the Fan Coil System
This  is  usually  accomplished  by  turning 
off  the  circuit  breaker  in  the  breaker 
panel. 
3. Determine Wiring
Configuration
• Remove the old thermostat from the wall to expose the wiring terminals.
• Take a picture of the wiring for future reference.
• Note the terminals attached to each wire and attach the matching label to the
ends of the wires. 
Use the following table as reference: 
Terminal 
Name 
Function 
4 pipe system 
2 pipe system 
24VAC input 
Common of AC input 
WY 
Hot water valve output 
Pipe valve output 
YA 
Chilled water valve output 
Auxiliary Heat (A) 
Gl 
Fan coil low speed control 
Gm 
Fan coil medium speed control 
Gh 
Fan coil high speed control 
Ac 
Accessory output (relay contact) 
Ac 
Accessory output (other side of relay) 
Tp 
Pipe temperature sensor input 
Tx 
External temperature sensor input 
Ts 
Setback contact input 
Tc 
Tx/Tp/Ts common 
4. Remove Old Thermostat Terminals
After all wires have been labeled, carefully 
remove the wiring and any mounting or back 
plate from the old thermostat.  
Tip: Wrap the wires around a pencil to prevent 
them from falling into the wall space 
Note: If you intend to paint the mounting 
surface, now is the best time to do so to insure 
complete wall coverage behind and around the 
thermostat without the use of a back plate.  
5. Install Wiring Mount
Remove the wiring mount from the packaging, and use the included wall screws 
and/or anchors to attach the wiring mount to the wall, making sure the wires run 
through the center opening. If alternate mounting holes are required, use a wall 
plate (sold separately).  
No box or horizontal single 
gang box 
Vertical single gang box 
(wall plate sold separately) 
2 gang (4” square) box 
(wall plate sold separately) 
6. Attach Wiring
Connect  the  labeled  wires  to  their  matching  terminals  based  on  the  fan  coil 
configuration as follows: 
Configuration 
R  C 
WY  YA 
Gl 
Gm 
Gh 
Ac 
Ac 
Tp 
Tx 
Ts  Tc* 
2-pipe Heat Only
√  √ 
√ 
√ 
√ 
2-pipe Cool Only
√  √ 
√ 
√ 
√ 
2-pipe Heat or Cool -
Manual changeover 
√  √  W/Y 
√ 
√ 
√ 
2-pipe Heat or Cool -
Seasonal changeover
√  √  W/Y 
√ 
√ 
√ 
√ 
√ 
2-pipe Heat or Cool with
Auxiliary Heat
√  √  W/Y 
√ 
√ 
√ 
√ 
√ 
4-pipe Heat / Cool, 
Manual or Auto changeover
√  √ 
√ 
√ 
√ 
√: Required 
O: Optional 
* If using more than one T terminal (Tp,Tx,Ts), it may be necessary to splice for Tc.
Wireless Fan Coil 
Controller 
SC102ZB 
Quick Start Guide 
Notices 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
• Follow all local and electricity supplier regulations regarding the installation or 
replacement of a thermostat. An authorized, qualified installer may be required. 
• Do not connect any of the terminals to a 120/240 VAC supply. The Wireless 
Fan Coil Controller uses a 24 VAC power source. 
• Do not cover any of the vents on the thermostat. 
• Do not place the unit in a bathroom or area of excessive moisture.
• Do not allow the unit to get wet. This device serves as a temperature control 
system only in dry, closed living and office spaces. 
• Do  not  use  solvents  or  aggressive  cleaning  agents.  A  dry,  soft  cloth  is 
recommended.
The manufacturer does not accept responsibility for any damage caused by not 
following these instructions. 
1. Let’s Get Started
Make sure you have the following items: 
Controller with 
Wiring Mount 
Wiring Labels 
Screws and 
Anchors 
Quick Start Guide 
Tools: 
• #1 Phillips or flathead 
screwdriver 
• Drill with 3/16” bit
(only if you need to use 
anchors) 
 
 
   
 
   
 
 
 
 
 
 
 
   
 
 
 
 
 
 
Please read these instructions carefully before installing and using the Wireless 
Fan Coil Controller.
 
•  Smartphone or digital camera to take picture
  of wiring for later reference
•  Screwdriver to disconnect wires from old
  thermostat
•  Pencil
Optional Tools: