PROTECTION
Overload protection
Overload (above 105%) is indicated by a continuous sound and a corresponding message on the 
display.
If the overload is 105-120%, then the power supply unit will remain in the previous mode for one minute 
before switching to BYPASS. If the overload exceeds 120% of the nominal power rating, the BYPASS mode 
is  switched  on  immediately. The  unit  remains  in  BYPASS  as  long  as  the  overload  continues  above  the 
predefined limit. Once the overload discontinues, the unit attempts to restart five times. If they fail, the unit 
switches to EMERGENCY mode. In BACKUP mode, an overload causes the unit to switch to EMERGENCY 
mode without any additional attempts to restart.
Short circuit protection
A short circuit is indicated by 
a corresponding message and a quick, intermittent beep If the short circuit lasts longer than a predefined limit 
(hundreds of milliseconds), the unit switches to EMERGENCY mode.
Surge protection
The unit features surge protection at the input, which protects the receiver circuits and internal circuitry 
against  high  energy  voltage  surges  caused  by  atmospheric  phenomena  and  interference  in  the  power 
network.
Battery protection
Batteries are protected with fusible links. The connection of the external battery pack (optional) features an 
additional safeguard, as do the internal batteries. The safety device also serves as a disconnecting switch 
that can be used during assembly.
Thermal protection
The unit is equipped with a thermal safeguard that protects it against overheating. There are two levels of 
protection. If the internal temperature approximates a critical value, then a sound is emitted and a message is 
displayed on the screen.
If the temperature keeps increasing, at the 
critical value an alert message is displayed and the unit switches to EMERGENCY mode.
 
 
 
 
 
In the inverter-based modes, i.e. NORMAL, BACKUP, and HIBRID, there is an electronic short circuit protection 
that in case of a short circuit limits, the short circuit current returns to its safe level. 
 
 
 
 
 The unit remains in the current mode. 
NOTE!  It  is  forbidden  to  use  fuse  links  other  than  those  listed  in  the  device 
specification.
!