Ever Poweline 33 30kVA/24kW W/PWRLTO-3330K0/00 Manual Do Utilizador
Códigos do produto
W/PWRLTO-3330K0/00
When selecting the place of installation, consider the weight of the device. The UPS should only be used in rooms where
the dust, temperature, and humidity levels are within the device specifications. Appropriate cooling conditions must be
ensured for the UPS to work correctly. For this reason, the ventilation openings of the UPS must be uncovered at all
times, and the distance between the UPS and other objects should not be less than 30 cm.
the dust, temperature, and humidity levels are within the device specifications. Appropriate cooling conditions must be
ensured for the UPS to work correctly. For this reason, the ventilation openings of the UPS must be uncovered at all
times, and the distance between the UPS and other objects should not be less than 30 cm.
Detailed information is provided in a separate installation guidelines document that is enclosed with the
product.
product.
CONNECTING THE UPS
INSTALLATION GUIDELINES
PARAMETER/MODEL
POWER SUPPLY PARAMETERS
ENVIRONMENTAL PARAMETERS
MECHANICAL PARAMETERS
OUTPUT PARAMETERS
Output power
1)
10kVA/10kW
~400V
400V
3P5W
3P5W
o
10÷40 C
o
0÷40 C
<1000 m
270 kg
<95%
Model 10k
Model 20k
Model 30k
Model 40k
Model 50k
20kVA/16kW
30kVA/24kW
40kVA/32kW
50kVA/35kW
Supply system topology
Output system topology
Quantity of heat released
for nominal work conditions
for nominal work conditions
Nominal output voltage
Rated current
Rated voltage
Rated current
BYPASS
line protection
line protection
BYPASS
line protection
line protection
Output
line protection
line protection
Switch
disconnector
disconnector
Switch fuse
Switch fuse
Working temperature
Storage temperature
Humidity
Rated input frequency
Minimum wire section surface area
Minimum wire section surface area
Altitude (above sea level)
POWERLINE 33
2
2,5mm
2
2,5mm
25 A gG
25 A gG
25 A gG
50 A gG
50 A gG
80 A gG
80 A gG
100 A gG
100 A gG
100 A gG
100 A gG
2
6mm
2
6mm
2
10mm
2
10mm
2
16mm
2
16mm
2
16mm
2
16mm
Dimensions
(width x depth x height)
1)
UPS weight
Operating distance
Notes:
1)
Weight for the typical battery set-up 1x 2x 32x VRLA 12V /7Ah. Weight depends on the type and number of batteries.
405x840x1040mm
Front: >200 mm
Sides: >100 mm
Back: >300 mm
Sides: >100 mm
Back: >300 mm
18 A
15 A
25 A
< 2100 BTU
< 3300 BTU
< 5000 BTU
< 6600 BTU
< 7200 BTU
50 A
80 A
100 A
100 A
29 A
44 A
58 A
73 A
28 A
41 A
50 A
55 A
60 A
www.ever.eu
10-33, 20-33, 30-33, 40-33, 50-33
POWERLINE 3-3