Moog Videolarm SPVP110 Folheto
ALARM/CONTROL PANEL INSTALLATION
DIAGRAM #1
ALARM/CONTROL PANEL
Circuit Board
Battery
Battery
120VAC Power In
SPVP110-120HW
ELECTRICAL PANEL/DISCONNECT INSTALLATION
DIAGRAM #2
SPVP110-120HW
Black Wire
Neutral Bus
White Wire
Green Wire
Ground Bus
www.videolarm.com
S P V P 1 1 0 / 2 2 0
Video Surge Protection
Installation and Operation Instructions for the following model:
81-IN5404
12-23-2011
SPVP110
110Vac power surge protection
Before attempting to connect or operate this product, please read these instructions completely.
© 2011, Moog Videolarm, Inc. All Rights Reserved
This Surge Protection Device (SPD) is a high performance device, designed to
provide protection for sensitive electronic loads connected to service panels,
fire panels, or where the SPD is directly connected to the electronic device.
Maximum protection will only be achieved if the SPD is properly installed.
provide protection for sensitive electronic loads connected to service panels,
fire panels, or where the SPD is directly connected to the electronic device.
Maximum protection will only be achieved if the SPD is properly installed.
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed by a qualified electrician in accordance
with the National and Local Electrical Codes and the following instructions.
with the National and Local Electrical Codes and the following instructions.
APPLICATION
Surge suppression for hard wired parallel installations on 120 VAC single
branch circuits.
Surge suppression for hard wired parallel installations on 120 VAC single
branch circuits.
INSTRUCTIONS:
Caution:
Measure all voltages to insure applied voltage does not exceed the
voltage rating of the unit. Improper installation voids the warranty.
1. Turn o the power at the circuit breaker or main before beginning installation.
2. If necessary, remove front cover from the panel.
2. If necessary, remove front cover from the panel.
3. Remove ½” knockout on side of panel box.
4. Unscrew nut from unit.
5. Feed all wires and the SPVP110 nipple through knockout hole then through
nut, tighten nut securing the unit as shown.
nut, tighten nut securing the unit as shown.
6. For alarm/control panel installation, refer to diagram #1. In this application,
make sure the leads are as short as possible to the connection point ( isolated
lugs or terminal). Also, allow the unit reaction time by allowing no less than
2’ of conductor length between the 120HW and the panel it is protecting.
make sure the leads are as short as possible to the connection point ( isolated
lugs or terminal). Also, allow the unit reaction time by allowing no less than
2’ of conductor length between the 120HW and the panel it is protecting.
7. For electrical panel/disconnect installation, refer to diagram #2. In this
application, connect the SPVP110 to the load side of the fuse or circuit
breaker. Also, make sure the leads are as short as possible with ground
wire being the shortest of all. Ground Resistance Rule: Max ground
resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an
assumed value and must be measured to assure proper grounding.
application, connect the SPVP110 to the load side of the fuse or circuit
breaker. Also, make sure the leads are as short as possible with ground
wire being the shortest of all. Ground Resistance Rule: Max ground
resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an
assumed value and must be measured to assure proper grounding.
8. After all connections have been made and no hazards exist, restore power.
9. This device is suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amps, 120 volts maximum. The interrupting rating
of the fuse or circuit breaker shall not be less than the available fault current.
10,000 rms symmetrical amps, 120 volts maximum. The interrupting rating
of the fuse or circuit breaker shall not be less than the available fault current.