Toshiba VF-AS1 Manual Do Utilizador
!
E6581301
J-3
10
■
■
■
■ Selection of wiring equipment
Voltage
class
Applicable
motor [kW]
Inverter model
Input current[A]
Molded Case Circuit Breaker
(MCCB)
Magnetic contactor
(MC)
Without
Reactor
With
Reactor
Without
Reactor
Reactor
With
Reactor
Without
Reactor
With
Reactor
Rated current
[A]
Rated current
[A]
Operationl
current [A]
current [A]
AC-1
Operationl
current [A]
current [A]
AC-1
200V
class
0.4
VFAS1-2004PL
3.5
2.1
5
5
25
25
0.75
VFAS1-2007PL
6.1
3.2
10
5
25
25
1.5
VFAS1-2015PL
11.3
6.4
15
10
25
25
2.2
VFAS1-2022PL
15
9.3
20
15
25
25
3.7/4.0
VFAS1-2037PL
25.8
15.5
30
30
32
25
5.5
VFAS1-2055PL
35
22. 5
50
40
40
25
7.5
VFAS1-2075PL
45
34.5
60
40
50
40
11
VFAS1-2110PM
-
53.3
-
75
-
80
15
VFAS1-2150PM
-!
71.7
-!
100
-!
80
18.5
VFAS1-2185PM
-!
77
-!
100
-!
80
22
VFAS1-2220PM
-!
88
-!
125
-!
125
30
VFAS1-2300PM
-!
124
-!
150
-!
125
37
VFAS1-2370PM
-!
141
-!
175
-!
250
45
VFAS1-2450PM
-!
167
-!
200
-!
250
55
VFAS1-2550P
-!
200
-!
250
-!
275
75
VFAS1-2750P
-!
271
-!
350
-!
350
400V
class
0.75
VFAS1-4007PL
3.7
2.1
5
4
25
25
1.5
VFAS1-4015PL
5.8
3.8
10
6.3
25
25
2.2
VFAS1-4022PL
8.2
5.7
14
10
25
25
3.7/4.0
VFAS1-4037PL
14.1
8.7
18
14
25
25
5.5
VFAS1-4055PL
20.3
12.7
32
25
25
25
7.5
VFAS1-4075PL
27
16.3
32
25
32
25
11
VFAS1-4110PL
36.6
21.5
50
30
40
32
15
VFAS1-4150PL
48
33.5
60
40
50
40
18.5
VFAS1-4185PL
-
45.5
-
60
-
50
22
VFAS1-4220PL
-!
50
-!
60
-!
50
30
VFAS1-4300PL
-!
66
-!
100
-!
80
37
VFAS1-4370PL
-!
84
-!
100
-!
125
45
VFAS1-4450PL
-!
104
-!
125
-!
125
55
VFAS1-4550PL
-!
120
-!
150
-!
125
75
VFAS1-4750PL
-!
167
-!
200
-!
250
90
VFAS1-4900PC
-!
166
-!
200
-!
250
110
VFAS1-4110KPC
-!
202
-!
250
-!
275
132
VFAS1-4132KPC
-!
238
-!
300
-!
315
160
VFAS1-4160KPC
-!
289
-!
350
-!
350
200
VFAS1-4200KPC
-!
356
-!
500
-!
500
220
VFAS1-4220KPC
-!
396
-!
500
-!
500
280
VFAS1-4280KPC
-!
494
-!
700
-!
700
355
VFAS1-4355KPC
-!
636
-!
1000
-!
1000
400
VFAS1-4400KPC
-!
707
-!
1000
-!
1000
500
VFAS1-4500KPC
-!
875
-!
1200
-!
1600
(*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
(*2): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*3): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current
for the motor rated current.
(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*5): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability
of the contact by using 2a-type contacts in parallel connection.
(*6): For 200V/55kW model and larger and 400V/90kW model and larger, be sure to install a DC reactor.