Tripp Lite SMART750 Manual Do Utilizador

Página de 5
Overvoltage
correction
Input voltages between 128 and 147V AC are reduced by 12%
Direct pass
through
Input voltages between 108 and 127V AC are passed on to connected equipment unchanged
Brownout
correction
Input voltages between 93 and 107V AC are boosted by 14%
Severe brownout
correction
Input voltages between 75 and 92V AC are boosted by 30%
LEDS ALARMS & SWITCHES
Front panel LEDs
Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE
REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
Alarms
Audible alarm with 15-second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel
alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches
Includes 2 front panel switches--one main on/off power switch and one dual function "alarm cancel" / "self test" button
SURGE / NOISE SUPPRESSION
AC surge
suppression
510 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight
(lbs)
25
Shipping weight
(kg)
10.9
Shipping
Dimensions
(HWD/in)
15.5 x 11 x 11.25
Shipping
Dimensions
(HWD/cm)
39.4 x 28 x 28.6
Unit weight (lbs)
23
Unit weight (kg)
10.0
Unit Dimensions
(HWD/in)
11.75 x 7.25 x 7.5
Unit Dimensions
(HWD/cm)
29.8 x 18.4 x 19.1
Material of
construction
PVC
Form factors
supported
Tower
Cooling method
Convection
Battery Access
Battery access door allows user replacement of UPS batteries
ENVIRONMENTAL
Relative Humidity
0 to 95%, non-condensing
Storage
Temperature
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
COMMUNICATIONS