NEMA PE 1, " Uninterruptible Power Systems (UPS) - Specification and Performance
Verification."
Verification."
E.
National Fire Protection Association (NFPA):
1.
1.
NFPA 70, "National Electrical Code" (copyrighted by NFPA, ANSI approved) - hereinafter
referred to as NEC.
referred to as NEC.
F.
Underwriters Laboratories, Inc. (UL):
1.
1.
UL 1778, "Standard for Uninterruptible Power Supply Equipment" (copyrighted by UL,
ANSI approved). “
ANSI approved). “
2.
UL 924, “Emergency Lighting and Power Equipment”
1.4 SYSTEM
DESCRIPTION
A.
UPS Design Requirements:
INSERT kVA BELOW.
1.
Output Power Continuous Rating: The continuous output power rating of the UPS shall
be [_____] kVA at a 0.9 lagging power factor.
be [_____] kVA at a 0.9 lagging power factor.
2.
Field-Powered Upgrade: The following power ratings may be upgraded in the field to
provide more output power with no increase in footprint:
a. 40 kVA/36 kW UPS modules shall upgrade to 50 kVA/45 kW.
b. 60 kVA/54 kW UPS modules shall upgrade to 80 kVA/72 kW.
c. 100 kVA/90 kW UPS modules shall upgrade to 130 kVA/117 kW.
provide more output power with no increase in footprint:
a. 40 kVA/36 kW UPS modules shall upgrade to 50 kVA/45 kW.
b. 60 kVA/54 kW UPS modules shall upgrade to 80 kVA/72 kW.
c. 100 kVA/90 kW UPS modules shall upgrade to 130 kVA/117 kW.
INSERT VOLTS BELOW.
3.
Input Voltage: [___] volts AC, -15 percent +10 percent, three-phase, 3 wires, grounded
wye, configuration plus ground.
a. 480 volts standard.
b. 208 volts, 220 volts, 600 volts with optional transformer.
wye, configuration plus ground.
a. 480 volts standard.
b. 208 volts, 220 volts, 600 volts with optional transformer.
INSERT VOLTS BELOW.
4.
Output Voltage: [___] volts AC, three-phase, 3 wires plus ground.
a. 480 volts standard.
b. 208 volts, 220 volts, 600 volts with optional transformer.
c. 4 wire output shall be derived within the UPS system and provided as needed at
a. 480 volts standard.
b. 208 volts, 220 volts, 600 volts with optional transformer.
c. 4 wire output shall be derived within the UPS system and provided as needed at
480/277 or 208/120 with optional transformer.
INSERT AMPS BELOW.
5.
Input Current: [___] amps @ 480 volts AC maximum charging
6.
Output Current: [___] amps @ 480 volts AC
INSERT MINUTES BELOW.
7.
Battery Autonomy: UPS shall be capable of operating at full load for [_____] minutes at
0.9 PF output at a temperature of 77 °F (25 °C) on battery power.
0.9 PF output at a temperature of 77 °F (25 °C) on battery power.
8.
Battery Type: Valve regulated sealed lead acid (VRLA).
B.
AC Input Characteristics:
INSERT VOLTS BELOW.
1.
Voltage: [___] volts AC, -15 percent +10 percent, three-phase, 3 wires, grounded wye,
configuration plus ground.
configuration plus ground.
2.
Frequency: 60 hertz, ±5 percent.
3.
Power Factor: Greater than 0.98 lagging.
4.
Total Harmonic Distortion: Less than 5 percent at full load.
5.
Inrush Current: Less than nominal input current for less than one cycle.