12/10/13 
manufacturer shall conduct inspections on incoming parts, modular assemblies, and final 
products. 
 
1.7   
DELIVERY, STORAGE, AND HANDLING 
 
A. 
Deliver materials to the Project site in supplier’s or manufacturer’s original wrappings and 
containers, labeled with supplier’s or manufacturer’s name, material or product brand name, and 
lot number, if any. 
 
B. 
Store materials in their original, undamaged packages and containers, inside a well-ventilated 
area protected from weather, moisture, soiling, extreme temperatures, and humidity. 
 
C. 
Products shall be packaged in a manner to prevent penetration by debris and to allow safe 
delivery by modes of ground transportation and air transportation where specified. 
 
D. 
Prior to shipping, products shall be inspected at the factory for damage. 
 
E. 
Equipment shall be protected against extreme temperature and humidity and shall be stored in a 
conditioned or protected environment. 
 
F. 
Equipment containing batteries shall not be stored for a period exceeding three months without 
powering up the equipment for a period of eight hours to recharge the batteries. 
 
1.8   PROJECT 
CONDITIONS 
 
A. 
Environmental Requirements:  Do not install solid state UPS until space is enclosed and 
weatherproof, wet work in space is completed and nominally dry, work above ceilings is 
complete, and ambient temperature and humidity conditions are and will be continuously 
maintained at values near those indicated for final occupancy. 
1. 
The UPS shall operate under the following environmental conditions: 
a.  Temperature: 
1)  UPS Module Operating:  32 °F (0 °C) to 104 °F (40 °C). 
2)  Non-Operating:  -4 °F (-20 °C) to 113 °F (45 °C). 
b.  Relative Humidity (Operating and Storage):  0 percent to 95 percent 
non-condensing. 
c.  Barometric Pressure:  Up to 3281 feet (1000 meters) above sea level (up to 
6562 feet [2000 meters] with ambient temperature less than 82 °F [28 °C]) / up to 
39,370 feet (12,000 meters) above sea level non-operating. 
d.  Audible Noise:  69 dBA at 3 feet (914 mm). 
 
1.9   WARRANTY 
 
A. 
General:  See [Section 01 77 00 - CLOSEOUT PROCEDURES] [Section 01770 - CLOSEOUT 
PROCEDURES]. 
 
B. 
Special Warranty:  The Contractor shall warrant the work of this Section to be in accordance 
with the Contract Documents and free from faults and defects in materials and workmanship for 
period indicated below.  This special warranty shall extend the one year period of limitations 
contained in the General Conditions.  The special warranty shall be countersigned by the 
Installer and the manufacturer. 
1. 
UPS Module:  The UPS shall be covered by a full parts and labor warranty from the 
manufacturer for a period of 12 months from date of installation or acceptance by the 
Owner or 18 months from date of shipment from the manufacturer, whichever occurs first. 
2. 
Battery:  The battery manufacturer’s warranty shall be passed through to the final Owner 
and shall have a minimum period of one year. 
 
C. 
Additional Owner Rights:  The warranty shall not deprive the Owner of other rights the Owner 
may have under other provisions of the Contract Documents and shall be in addition to and run 
concurrent with other warranties made by the Contractor under requirements of the Contract 
Documents. 
 
1.10   MAINTENANCE