FSP/Fortron Knight KN-1102TS KN-1102TS Ficha De Dados

Códigos do produto
KN-1102TS
Página de 2
 
 
 
 
 Input
 
 
 
 Voltage
 Range
Low Line Transfer
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
168 VAC / 148 VAC / 128VAC / 118 VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
High Line Transfer
300 VAC ± 5 % or 150 VAC ± 5 %
High Line Comeback
290 VAC ± 5 % or 145 VAC ± 5 %
 Frequency Range
40Hz ~ 70 Hz
 Phase
Single phase with ground
 Power Factor
≧ 0.99 @ Nominal Voltage (100% load)
 
 Output
 Output Voltage
00/208/220/230/240VAC
 Voltage Regulation
± 1%
 Frequency range
 (Synchronized Range)
47~ 53 Hz or 57 ~ 63 Hz
 Frequency Range
 (Batt. Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
 Overload
N/A
 Current Crest Ratio
3:1
 Harmonic Distortion
≦ 2 % THD (Linear Load)
≦ 4 % THD (Non-linear Load)
 Bypass to Inverter
4 ms (Typical)
 Waveform (Batt. Mode)
Pure Sinewave
 
 
 
 
 
 Efficiency
 AC Mode
87%
90%
90%
 Battery Mode
83%
87%
89%
 
 
 
 
 
 Battery
 Standard
 Backup
Battery Type
12V / 1 Ah
12V / 7Ah
12V / 9Ah
Numbers
3
6
6
Typical Recharge Time
4 hours recover to 90% capacity
Charging Current
(max.)
1.0 A
Charging Voltage
41.0 VDC ± 1%
82.1 VDC ± 1%
82.1 VDC ± 1%
 
 
 
 
 
 Indicators
 LCD or LED
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
 
 
 
 
 
 Alarm
 Battery Mode
Sounding every 4 seconds
 Low Battery
Sounding every second
 Overload
Sounding twice every second
 Fault
Continously sounding
 
 
 
 
 
 AC Input & Output Connectors
 AC Input Connector
1 x IEC 320 C14
1 x IEC 320 C14
1 x IEC 320 C20
 AC Output Connector
4 x IEC 320 C13
8 x IEC 320 C13
6 x IEC 320 C13 / 1 x IEC C19
 
 
 
 
 
 Standards
 IEC 62040-1 (safety)
Yes
 IEC-62040-2 (EMC)
Yes
 CE
Yes
 
 
 
 
 
 Physical dimensions
 Standard
 Model
Dimension (mm)
397 (D) x 145 (W) x 220 (H)
419 (D) x 119 (W) x 318 (H)
419 (D) x 119 (W) x 318 (H)
Net Weight (kgs)
13
26
28
 
 
 
 
 
 Environment
 Humidity
20-90% RH @ 0-40°C (non-condensing)
 Noise Level
Less tahn 50dBa @ 1 Meter
 
 
 
 
 
 Management
 Smart RS-232 / USB
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
 Optional SNMP
Power management from SNMP manager and web browser
 *Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC