Phoenix Contact Surge protection adapter plug Surge protection Black 2856993 Ficha De Dados

Códigos do produto
2856993
Página de 5
Nov 13, 2013    2 / 5
Technical data
Protective circuit
IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
D1
Maximum continuous operating voltage U
C
180 V DC
Maximum continuous operating voltage U
C
130 V AC
Maximum continuous voltage U
C
 (wire-shield)
180 V DC
Nominal current I
N
1.5 A (25 °C)
Operating effective current I
C
 at U
C
≤ 1 µA
Nominal discharge current I
n
 (8/20) µs (Core-Shield)
2.5 kA
Total surge current (8/20) µs
2.5 kA
Nominal pulse current Ian (10/1000) µs (Core-Shield)
120 A
Output voltage limitation at 1 kV/µs (Core-Shield) spike
≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Shield) static
≤ 600 V
Residual voltage at In, (conductor-shield)
≤ 30 V
Voltage protection level U
P
 (Core-Shield)
≤ 700 V (C2 (4 kV/2 kA))
Response time tA (Core-GND)
≤ 100 ns
Input attenuation aE, asym.
0.5 dB (≤ 2.4 GHz)
Cut-off frequency fg (3 dB), asym. (shield) in 75 Ohm system
> 3 GHz
Frequency range
4.7 MHz ... 2.5 GHz
Capacity asymmetrical (shield)
typ. 10 pF
Surge carrying capacity in acc. with IEC 61643-21 (Core-
Shield)
C2 (4 kV / 2 kA)
Surge carrying capacity in acc. with IEC 61643-21 (Core-
Shield)
C3 (100 A)
Surge carrying capacity in acc. with IEC 61643-21 (Core-
Shield)
D1 (500 A)
Alternating current carrying capacity in acc. with IEC 61643-21
(Core-Shield)
5 A - 1 s
Connection data
Connection method
F connector
Connection type IN
F connector, female
Connection type OUT
F connector, female
Standards and Regulations
Standards/regulations
IEC 61643-21
Standards/regulations
EN 50083 - CLASS A
classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801