Measuring Continuity 
R
LO
 
apx003f.eps 
Figure 10. Continuity Zero Display/Switch and Terminal Settings 
A continuity test is used to verify the integrity of connections by making a high 
resolution resistance measurement. This is especially important for checking 
Protective Earth connections.  
Note 
In countries where electrical circuits are laid out in a ring, it is 
recommended that you make an end-to-end check of the ring at the 
electrical panel. 

 Warning 
 
Measurements should only be performed on de-energized 
circuits. 
 
Measurements may be adversely affected by impedances or 
parallel circuits or transient currents. 
To measure continuity: 
1.  Turn the rotary switch to the R
LO
 position. 
2.  Use the L and PE (red and green) terminals for this test. 
3.  Before making a continuity test, use the Zero adapter to zero the test 
leads. Press and hold  until the ZERO annunciator appears. The 
tester measures probe resistance, stores the reading in memory, and 
subtracts it from readings. The resistance value is saved even when power 
is turned off so you don’t need to repeat the operation every time you use 
the instrument.