Fluke 1653B04-TPOLEKIT/FVDE-tester 4426025 Manual Do Utilizador

Códigos do produto
4426025
Página de 66
 Electrical 
Installation 
Tester 
 Operating 
the 
Tester 
17 
Power-On Options 
To select a power-on option, press  and the function key simultaneously and 
then release the  button. Power-on options are retained when the tester is 
turned OFF. See Table 8. 
Table 8. Power-On Options 
Keys  
Power-On Options 
  
Loop/Line Impedance I
limit. Toggles the I
K
 limit between 10 kA 
and 50 kA. The default is 10 kA. 
  
Line and Neutral Swap mode. Two modes of operation are 
available. You can configure the tester to operate in L-n mode or 
L-n n-L mode, see Figure 7. 
  In L-n mode, the L and N phase conductors must NEVER be 
reversed. This is a requirement in some regions including the 
UK. The  icon appears on the display indicating that the 
system L and N conductors are swapped and testing is 
inhibited. Investigate and rectify the cause of this system fault 
before proceeding. L-n mode also changes the RCD x1/2 trip 
time duration to 2 seconds as required in the UK. 
  In L-n n-L mode, the unit allows the L and N phase conductors 
to be swapped and testing will continue. 
Note 
In locations where polarized plugs and outlets are used, a 
swapped lead icon 
() may indicate that the outlet was 
wired incorrectly. Correct this problem before proceeding 
with any testing. 
  
Fault voltage limit. Toggles the fault voltage between 25 V and 50 
V. The default is 50 V. 
  
View the tester serial number. Primary display shows the initial 
four digits and the secondary display shows the next four digits.