 Specifications 
45 
General Specifications 
Specification Characteristic 
Size 
10 cm (L) x 25 cm (W) x 12.5 cm (H) 
Weight (with batteries) 
1.3 kg 
Battery size, quantity 
Type AA, 6 ea. 
Battery type 
Alkaline supplied. 
Usable with 1.2 V NiCd or NiMH batteries (not supplied) 
Battery life (typical) 
200 hours idling 
Fuse 
T3.15 A, 500 V, 1.5 kA 6.3 x 32 mm (PN 2030852) 
Operating Temperature 
-10 
°
C to 40 
°
Storage Temperature 
-10 
°
C to 60 
°
C indefinitely (to -40 
°
C for 100 hrs) 
Relative Humidity 
80 % 10 to 35 
°
C; 70 % 35 to 40 
°
Operating Altitude 
0 to 2000 meters 
Shock, Vibration 
Vibration to Class 3 per Mil-Prf-28800F 
1 meter drop test, six sides, oak floor 
Sealing 
IP 40  
EMC 
Complies with EN61326-1: 2006 
Safety 
Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, 
ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 
No.1010 2
nd
 edition 
Overvoltage Category: 500 V/CAT III  
 300 V/CAT IV 
Measurement Category III is for measurements 
performed in the building installation. Examples are 
distribution panels, circuit breakers, wiring and cabling. 
Category IV equipment is designed to protect against 
transients from the primary supply level, such as an 
electrical meter or an overhead or underground utility 
service. 
Performance EN61557-1, EN61557-2, EN61557-3, 
EN61557-4, EN61557-5, EN61557-6, EN61557-7 
Second edition. EN61557-10 First edition. 
Pollution Degree 
Maximum voltage between any 
terminal and earth ground  
500 V 
Surge Protection 
6 kV peak per EN 61010-1 Ed. 2.0 (2001-02)