57
Operating Ranges and Uncertainties per EN 61557
Function Display
Range
EN 61557
Measurement
Range Operating
Uncertainty
Nominal Values
V
EN 61557-1
EN 61557-1
0.0 V ac – 500 V ac
50 V ac – 500 V ac
±
(2% + 2 dgt)
U
N
= 230/400 V ac
f = 50/60 Hz
RLO
EN 61557-4
EN 61557-4
0.00
Ω
- 2000
Ω
0.2
Ω
- 2000
Ω
±
(10 % + 2 dgt)
4.0 V dc <U
Q
<24 V dc
R
LO
≤
2.00
Ω
I
N
≥
200 mA
RISO
EN 61557-2
EN 61557-2
0.00 M
Ω
- 1000 M
Ω
1 M
Ω
- 200 M
Ω
±
(10 % + 2 dgt)
200 M
Ω
- 1000 M
Ω
±
(15 % + 2 dgt)
U
N
= 50 / 100 / 250 / 500
/ 1000 V dc
I
I
N
= 1.0 mA
Z
I
(No Trip)
0.00
Ω
- 2000
Ω
0.4
Ω
- 2000
Ω
±
(15
% + 6 dgt)
Z
I
(Hi Current)
0.00
Ω
- 2000
Ω
0.2
Ω
- 200
Ω
±
(10 % + 4 dgt)
Z
I
(Hi Current, Hi Res)
0 m
Ω
- 9999 m
Ω
100 m
Ω
- 9999 m
Ω
±
(8 % + 20 dgt)
ZI
EN 61557-3
EN 61557-3
R
E
0.00
Ω
- 2000
Ω
10
Ω
- 1000
Ω
±
(10 % + 2 dgt)
U
N
= 230/400 V ac
f = 50/60 Hz
I
I
K
= 0 A – 10.0 kA
Δ
T
0.0 ms – 2000 ms
25 ms – 2000 ms
±
(10 % + 1 dgt)
Δ
T = 10 / 30 / 100 / 300 /
500 / 1000 / VAR mA
Δ
T, I
Δ
N
EN 61557-6
I
Δ
N
3 mA – 550 mA
(VAR 3 mA – 700 mA)
(VAR 3 mA – 700 mA)
3 mA – 550 mA
±
(10 % + 1 dgt)
I
Δ
N
= 10 / 30 / 100 / 300 /
500 / VAR mA
RE
EN 61557-5
EN 61557-5
0.0
Ω
- 2000
Ω
10
Ω
- 2000
Ω
±
(10 % + 2 dgt)
f = 128 Hz
Phase
EN 61557-7
EN 61557-7
1 : 2 : 3