Hiquel SW1 Time Delay Relay, Timer, 24 V/AC/DC SW1 Ficha De Dados

Códigos do produto
SW1
Página de 1
0:00
overview
SW1/SW2
HIGH QUALITY ELECTRONICS
specification
ordering information
SW1 24Vac/dc
SW2 24Vac/dc
SPCO
SPCO
part no
supply
output
coil voltage 24V~=
SPCO output max. 10A
trigger input with 1/0/Auto switch
SW1
SW2
3,0V ON
2,5V OFF
7,0V ON
6,5V OFF
LED indicators for output
11.25mm DIN rail mount housing
coil voltage
duty cycle
nominal current
suppressor circuit
operating conditions
nominal voltage +10% / -15%
100%
15mA
freewheeling diode and varistor
-20 to +60 °C non condensing
24V~=
600mW
24V~=
600mW
trig
gerr
elayin12mmhousing
DIN
2.5V(6.5V)
(By SW2)
3V(7V)
1
0
A
A1
12
14
11
+YR
B1
B2
-A2
The output relay is controlled via terminals A1, A2
The output relay is controlled by the trigger
through terminals YR. The operating voltage
must be available continuously at terminal A1.
The relay is switched off. Input signals at terminals
A1 or YR are ineffective.
1. Switch position “1”:
2. Switch position “Auto”:
3. Switch position “0”:
1
1
in
12 B2
A1 A2
B1 YR
14 11
1
0
A
A2
A1
YR
12
14
1
1
B2
B1
+
~
-
~
Supply
U
A1-A2
=
>
=
>
2011
HIQUEL
B01.00
SW1/SW2
The SW triggers are designed to control pumps, fans, burners etc. They are
also designed to operate with an analogue 0-10VDC control signal.
Trigger Function
As soon as the input voltage reaches the operating threshold (ON), in AUTO
Mode, the relay pulls in.
If the input voltage falls below the cut off threshold (OFF), the relay drops out
again.
A manual control facility with feedback contact, (mode 1) is incorporated for
manual operation
The module can be operated in two modes which can be selected by the
three-position switch (Auto, 0, 1).
screw tightening torque
0,5Nm
on delay
off delay
switching voltage
input current
continuous current (detached)
min. switching capacity
max. switching frequency
<8ms
<25ms
250V~=
15A
10A@+20°C
>5mA
600/h
mechanical
electrical
Ie AC-15*
output relay spec.
Ie AC-15*
Ie DC-13*
1,5A
115V~
1,5A
230V~
1,5A
24V=
2 x 10 operations
6
1 x 10
5
operations
EN 60947-5-1
continuous current (attached)
3A@+60°C
Gehäusetypen
Gehäusetypen
Gehäusetype
housing type
12,00
60
41,5
60
60
16
O