Finder 15.51.8.230.0400 Pulse Relay With Dimmer 15.51.8.230.0400 Ficha De Dados
Códigos do produto
15.51.8.230.0400
Thermal protection and signaling
Thermal protection
Supply voltage
LED (15.81 type only)
OFF
ON
ON
—
—
ALARM
ALARM
The internal thermal protection (active on all dimmer types) will
detect an unsafe temperature, due to overload or incorrect
installation, and will turn the dimmer output off.
It is possible to turn the dimmer on, by push button, only when
the temperature reduces to a safe level (after 1 to 10 minutes,
depending on installation conditions) and after removing the
cause of the overload.
The internal thermal protection (active on all dimmer types) will
detect an unsafe temperature, due to overload or incorrect
installation, and will turn the dimmer output off.
It is possible to turn the dimmer on, by push button, only when
the temperature reduces to a safe level (after 1 to 10 minutes,
depending on installation conditions) and after removing the
cause of the overload.
3
15 Series - Electronic step relay and dimmer
Functions (15.51/15.91 types)
Type
Step dimming
Operating mode setup
Type 15.51
Operating mode 2 (without memory): on switch off, the light level is not memorized.
Long control pulse: The light level is progressively raised or
lowered through a maximum of 10 incremental steps.
lowered through a maximum of 10 incremental steps.
Short control pulse: Alternately switches On or Off between
the maximum light level and the off state.
the maximum light level and the off state.
Operating mode 1 (with memory): the previous light level is memorized.
Long control pulse: The light level is progressively raised or
lowered through a maximum of 10 incremental steps.
lowered through a maximum of 10 incremental steps.
Short control pulse: Alternately switches between On and Off.
When switching On, the light level assumes the value set
during the previous On state.
When switching On, the light level assumes the value set
during the previous On state.
On 15.51 operating mode 1 or 3 (with memory) is preset, but it is
possible to change it using the following sequence:
a) remove the supply voltage;
b) press the control button;
c) apply the supply to the relay, keeping the button closed for 3 second;
d) on button release, the light will flash twice to indicate the selection of
possible to change it using the following sequence:
a) remove the supply voltage;
b) press the control button;
c) apply the supply to the relay, keeping the button closed for 3 second;
d) on button release, the light will flash twice to indicate the selection of
operating mode 2 or 4, or flash once for operating mode 1 or 3.
Repeating the above steps will alternately change between operating
modes.
Repeating the above steps will alternately change between operating
modes.
Type 15.91
On 15.91 operating mode 4 (without memory) is preset, but it is
possible to change it using the following sequence:
a) remove the supply voltage;
b) press the control button;
c) apply the supply to the relay, keeping the button closed for 3 second;
d) on button release, the light will flash twice to indicate the selection of
possible to change it using the following sequence:
a) remove the supply voltage;
b) press the control button;
c) apply the supply to the relay, keeping the button closed for 3 second;
d) on button release, the light will flash twice to indicate the selection of
operating mode 3, or flash once for operating mode 4.
Repeating the above steps will alternately change between operating
modes.
Repeating the above steps will alternately change between operating
modes.
15.51...0400
15.51...0404
15.91...0000
15.91...0000
Operating mode 4 (without memory): on switch off, the light level is not memorized.
Long control pulse: The light level is progressively raised or
Lowered.
Lowered.
Short control pulse: Alternately switches On or Off between
the maximum light level and the off state.
the maximum light level and the off state.
Operating mode 3 (with memory): the previous light level is memorized.
Long control pulse: The light level is progressively raised or
lowered.
lowered.
Short control pulse: Alternately switches between On and Off.
When switching On, the light level assumes the value set
during the previous On state.
When switching On, the light level assumes the value set
during the previous On state.
Type
Linear dimming
II-2013, www
.finder
net.com
SERIE
15