Technical data
Input data
Current consumption
51.9 A (Maximum, mains operation)
Current consumption
10.6 mA (No load, mains operation)
Current consumption
6.9 A (Charging, mains operation)
Current consumption (maximum)
51.9 A (Maximum, mains operation)
Current consumption (idle)
10.6 mA (No load, mains operation)
Current consumption (charging process)
6.9 A (Charging, mains operation)
Buffer period
0.5 h (With battery module 38 AH)
Output data
Nominal output voltage
24 V DC
Output voltage range
18 V DC ... 30 V DC
Output current
40 A (-25 °C ... 50 °C)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, up to 2 modules with redundancy module
Connection in series
No
General
Net weight
0.7 kg
Efficiency
> 99 % (Mains operation, with charged power storage)
Efficiency
98 % (Battery operation)
Protection class
III
MTBF (IEC 61709, SN 29500)
> 500000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: horizontal 5 mm, vertical 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
UL approvals
UL/C-UL Recognized UL 60950
UL approvals
UL Listed UL 508
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
16 mm²
Conductor cross section stranded min.
0.5 mm²
Conductor cross section stranded max.
16 mm²
Conductor cross section AWG/kcmil min.
8
Conductor cross section AWG/kcmil max
6
Stripping length
10 mm