Weidmueller Weidmüller 8939680000 WAZ6 TTA Content: 1 pc(s) 8939680000 Ficha De Dados

Códigos do produto
8939680000
Página de 5
Data sheet...
 
WAVESERIES
WAZ6 TTA
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
 
 
Creation date November 19, 2012 2:38:27 PM CET
 
Catalogue status 06.11.2012 / We reserve the right to make technical changes.
2
Dimensions and weights
 
Length
100 mm
  Width
45 mm
Depth
112.4 mm
  Net weight
286 g
 
Temperatures
 
Operating temperature
-40 °C...+70 °C
  Storage temperature
-40 °C...+85 °C
 
Probability of failure
 
MTTF
138 Years
   
 
Input
 
Sensor supply
24 V DC / 22 mA
  Input frequency
2 Hz…100 kHz
Input current
-20...50 mA (min. span 0.4
mA)
  Resistance
10 Ω…5 kΩ
Sensor
Thermocouples: B, E, J, K,
L, N, R, S, T (IEC 60584),
PT100, PT1000, (EN
60571) Ni100, Ni1000,
(JIS1604), Cu10, Cu25,
Cu50, Cu100 (DIN 43760)
2-/3-/4-wire
  Potentiometer
100 Ω...100 kΩ
Input voltage
-200...500 mV (min. 4 mV
span), -20...50 V DC (min.
0.5 V span)
   
 
General data
 
Accuracy
< 0.1 % span (DC. RTD);
0.2 % span (or 1 °C) + CJ
failure
  Humidity
5...95 %, no condensation
Power consumption
< 3.5 W
  Step response time
50 ms...1 sec (RTD, mV
inputs), 110 ms...1 sec (V,
mA inputs)
Supply voltage
18...264 V AC/DC
  Temperature coefficient
< 0.1 % / K (DC, RTD);
< 0.1 % FSR / K +
CJ error 0.07 °C/K
(thermocouples )
Type of connection
Tension clamp connection    
 
Insulation coordination
 
Clearance & creepage distances
≥ 5.5 mm (1 mm 
Input/
output
)
  EMC standards
EN 55011, EN 61000-6
Impulse withstand voltage
6 kV
  Insulation voltage
2.5 kV
Pollution severity
2
  Rated voltage
300 V
Standards
DIN EN 50178, DIN EN
61000-4-2
  Surge voltage category
III
 
Output (analogue)
 
Signal output
direct or inverted
  Transmit function
Linear, x
1/2
, x
3/2
, x
5/2
 or
user-defined curve (101
points)