Weidmueller Weidmüller 8939680000 WAZ6 TTA Content: 1 pc(s) 8939680000 Ficha De Dados
Códigos do produto
8939680000
Data sheet...
WAVESERIES
WAZ6 TTA
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date November 19, 2012 2:38:27 PM CET
Catalogue status 06.11.2012 / We reserve the right to make technical changes.
2
Dimensions and weights
Length
100 mm
Width
45 mm
Depth
112.4 mm
Net weight
286 g
Temperatures
Operating temperature
-40 °C...+70 °C
Storage temperature
-40 °C...+85 °C
Probability of failure
MTTF
138 Years
Input
Sensor supply
24 V DC / 22 mA
Input frequency
2 Hz…100 kHz
Input current
-20...50 mA (min. span 0.4
mA)
Resistance
10 Ω…5 kΩ
Sensor
Thermocouples: B, E, J, K,
L, N, R, S, T (IEC 60584),
PT100, PT1000, (EN
60571) Ni100, Ni1000,
(JIS1604), Cu10, Cu25,
Cu50, Cu100 (DIN 43760)
2-/3-/4-wire
Potentiometer
100 Ω...100 kΩ
Input voltage
-200...500 mV (min. 4 mV
span), -20...50 V DC (min.
0.5 V span)
General data
Accuracy
< 0.1 % span (DC. RTD);
0.2 % span (or 1 °C) + CJ
failure
Humidity
5...95 %, no condensation
Power consumption
< 3.5 W
Step response time
50 ms...1 sec (RTD, mV
inputs), 110 ms...1 sec (V,
mA inputs)
Supply voltage
18...264 V AC/DC
Temperature coefficient
< 0.1 % / K (DC, RTD);
< 0.1 % FSR / K +
CJ error 0.07 °C/K
(thermocouples )
Type of connection
Tension clamp connection
Insulation coordination
Clearance & creepage distances
≥ 5.5 mm (1 mm
Input/
output
)
EMC standards
EN 55011, EN 61000-6
Impulse withstand voltage
6 kV
Insulation voltage
2.5 kV
Pollution severity
2
Rated voltage
300 V
Standards
DIN EN 50178, DIN EN
61000-4-2
Surge voltage category
III
Output (analogue)
Signal output
direct or inverted
Transmit function
Linear, x
1/2
, x
3/2
, x
5/2
or
user-defined curve (101
points)