Finder 39.31.0.125.0060 39.31.0.125.0060 39.31.0.125.0060 Ficha De Dados

Códigos do produto
39.31.0.125.0060
Página de 26
24
II-2014, www
.finder
net.com
Output fuse module for 39.31/30/81/80/61/60/91/90 types 
093.63
- For 5 x 20 mm fuses up to 6 A, 250 V
- Easy visibility of the fuse condition through the window
- Quick connection to socket
Notes
Safety: 
Because the output circuit can be reinstated (point 3 below), even with the fuse removed,  it is important not to
consider the removal of the fuse as a “safety disconnect”. Always isolate elsewhere before working on the circuit.
UL: According to UL508A, the fuse module cannot be installed in power circuits (in which it is mandatory that a fuse
certified according to UL category JDDZ be fitted). However, where the MasterInterface is connected as an output
interface to a PLC no such restrictions apply, and the fuse module can be usefully employed.
Multi-state fuse module
0. As delivered, the socket comes without a fuse module. However, the absent fuse is internally replaced with an electrical
link - which allows the interface relay to be used without a fuse module. 
In this state, the peg/indicator is visually hidden and the connection is protected by a special cap.
093.63
Accessories
3. In order to reinstate the output circuit it is necessary to either re-insert the fuse module (complete with functional fuse),
or alternatively, return the peg/indicator to position by gently applying pressure in the direction of the arrow.
2. If the fuse module is extracted (for example; because the fuse element has blown) the output circuit will be locked open,
as this will generally be the “safe option”.
This state is indicated by the peg/indicator.
1. With fuse module inserted after removing the cap, the fuse is positioned electrically in series with the common output
terminal of the interface  module (11 for EMR versions, 13+ for SSR versions, 15 for EMR timer, 15+ for SSR timer).
This state is indicated by the peg/indicator.
Approvals 
(according to type):
39
SERIE S
39 Series - Relay interface modules 0.1 - 2 - 6 A
B