Weidmueller Weidmüller 1180290000 TOS 120VAC/48VDC 0.5A RC Optocoupler Module, TERMOPTO 1180290000 Ficha De Dados
Códigos do produto
1180290000
Datenblatt
TERMOPTO
TOS 120VAC/48VDC 0.5A RC
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technische Daten
Erstellungs-Datum December 17, 2013 12:58:40 PM CET
Katalogstand xx.xx.xxxx / Technische Änderungen vorbehalten
2
Dimensions and weights
Width
6.1 mm
Height
74.5 mm
Depth
55 mm
Net weight
20.6 g
Temperatures
Humidity
5–95% rel. humidity, T
u
=
40°C, no condensation
Operating temperature
-20 °C...+60 °C
Storage temperature
-40 °C...+80 °C
Probability of failure
MTTF
2,500 Years
control side
Cut-in dropout voltage
102 V / 48 V AC
Rated control voltage
120 V AC ±20 %
Nominal control current
6.4 mA AC
Power rating
≤ 0.61 VA
Input frequency
< 10 Hz
Protective circuit, control side
RC element
Status display on control side
Green LED
Load side
Solid-state type
Transistor
Rated switching voltage
5...48 V DC
Continuous current
500 mA
Rated switching current
500 mA
Switch-on delay
< 12.6 ms
Switch-off delay
< 20.8 ms
Load category
DC1
Leakage current
< 10 µA
Protective circuit, load side
Diode
Voltage drop at max. load
< 1 V
Load side status indicator
No
Short-circuit-proof
No
General data
Solid-state type
Transistor
No. of poles
1
Wire connection method
Screw connection
Humidity
5–95% rel. humidity, T
u
=
40°C, no condensation
UL 94 flammability rating
V-0
Standards
DIN EN 50178, IEC
62314, UL508
Wire cross-section, solid, max.
2.5 mm²
Wire connection cross section, finely
stranded, max.
2.5 mm²
Insulation coordination
Rated voltage
300 V
Clearance and creepage distances for
control side - load side
> 3 mm
Dielectric strength for control side - load
side
1.2 kV
eff
/ 1 min.
Impulse withstand voltage
4 kV (1.2/50 µs)
Pollution severity
2
Surge voltage category
III
Further details of approvals
Standards
DIN EN 50178, IEC
62314, UL508