Weidmueller OPTO MOS 24VDC / 230VAC 1A 8652010000 Ficha De Dados

Códigos do produto
8652010000
Página de 7
Data sheet...
 
MICROSERIES
MOS 24Vdc/ 230VAC 1A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
 
 
Creation date November 19, 2012 2:25:57 PM CET
 
Catalogue status 06.11.2012 / We reserve the right to make technical changes.
2
Dimensions and weights
 
Width
6.1 mm
  Height
93 mm
Depth
94 mm
  Net weight
35.3 g
 
Temperatures
 
Operating temperature
-25 °C...+50 °C
  Storage temperature
-40 °C...+60 °C
 
Probability of failure
 
MTTF
314 Years
   
 
Connection data
 
Clamping range, rated connection
2.5 mm²
  Clamping range, rated connection, min. 0.5 mm²
Clamping range, rated connection, max. 4 mm²
   
 
Control side
 
Rated control voltage
24 V DC ±20 %
  Nominal control current
10.4 mA DC
Power rating
250 mW ± 15 %
  Input frequency
45 – 60 Hz
Cut-in (switch-on) voltage
≥ 17 V DC
  Dropout voltage
≤ 15.5 V DC
Protective circuit, control side
Reverse polarity protection,
Integrated free-wheel
diode
  Status display on control side
Green LED
 
Load side
 
Rated switching voltage
24...250 V AC
  Rated switching current
min. 20 mA / max. 1 A
Switch-on delay
< 11 ms
  Switch-off delay
< 11 ms
Leakage current
< 1.5 mA
  Voltage drop at max. load
≤ 1 V
Short-circuit-proof
No
   
 
General data
 
Solid-state type
Triac (no-voltage switch)   No. of poles
1
Conductor connection system
Screw connection
  Humidity
40 °C / 93 % rel. humidity,
no condensation
Standards
DIN EN 50178, UL508
   
 
Insulation coordination
 
Rated voltage
300 V
  Clearance and creepage distances for
control side - load side
≥ 5.5 mm
Dielectric strength for control side - load
side
2.5 KV
eff
 / 1 min.
  Dielectric strength to mounting rail
4 kV
eff
 / 1 min.
Impulse withstand voltage
4 kV (1.2/50 µs)
  Pollution severity
2
Surge voltage category
III
   
 
Further details of approvals
 
Standards