Phoenix Contact Surge protection connector PT 2X1VA- 60AC-ST 2839172 2839172 Ficha De Dados

Códigos do produto
2839172
Página de 8
Nov 13, 2013    2 / 8
Technical data
General
Color
black
Standards for air and creepage distances
VDE 0110-1
Standards for air and creepage distances
IEC 60664-1
Mounting type
On base element
Design
DIN rail module, two-section, divisible
Direction of action
Line-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software
version:
From SW rev. 1.00
Protective circuit
IEC test classification
C2
Nominal voltage U
N
60 V AC
Maximum continuous operating voltage U
C
100 V DC
Maximum continuous operating voltage U
C
75 V AC
Maximum continuous voltage U
C
 (wire-ground)
100 V DC
Maximum continuous voltage U
C
 (wire-ground)
75 V AC
Nominal current I
N
26 A (30 °C)
Operating effective current I
C
 at U
C
≤ 1.5 mA
Residual current I
PE
≤ 3 mA
Nominal discharge current I
n
 (8/20) µs
2 kA (C2 - 4 kV/2 kA)
Nominal discharge current I
n
 (8/20) µs (Core-Earth)
2 kA (C2 - 4 kV/2 kA)
Total surge current (8/20) µs
4 kA
Max. discharge current I
max
 (8/20) µs maximum (Core-Earth)
6.5 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 200 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 200 V
Output voltage limitation at 1 kV/µs (Core-Earth) static
≤ 200 V
Residual voltage at I
n
, (conductor-ground)
≤ 300 V
Enery absorption, asymmetrical
40 J
Voltage protection level U
P
 (Core-Earth)
≤ 300 V
Response time tA (Core-Earth)
≤ 25 ns
Message: Surge protection fault
Optical, remote indicator contact
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C2 (4 kV / 2 kA)
Connection data
Connection method
Screw connection (in connection with the base element)
Connection type IN
PLUGTRAB plug-in system
Connection type OUT
PLUGTRAB plug-in system
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²