Phoenix Contact Surge protection connector CT 10-18FS+F/PE-24 2807926 2807926 Ficha De Dados

Códigos do produto
2807926
Página de 4
Nov 13, 2013    2 / 4
Technical data
General
Arrester can be tested with CHECKMASTER from software
version:
From SW rev. 1.00
Protective circuit
IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
D1
Nominal voltage U
N
24 V DC
Maximum continuous operating voltage U
C
40 V DC
Maximum continuous operating voltage U
C
28 V AC
Maximum continuous voltage U
C
 (wire-GND)
40 V DC
Maximum continuous voltage U
C
 (wire-GND)
28 V AC
Nominal current I
N
1.5 A (75°C)
Operating effective current I
C
 at U
C
5 µA (18x)
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
 (8/20) µs (Core-Core)
214 A (25 °C)
Nominal discharge current I
n
 (8/20) µs (Core-Earth)
5 kA
Total surge current (8/20) µs
10 kA
Max. discharge current I
max
 (8/20) µs
119 A (25 °C)
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 60 V
Output voltage limitation at 1 kV/µs (Core-Earth) static
≤ 650 V
Residual voltage at I
n
, (conductor-conductor)
≤ 85 V (a-b)
Residual voltage at In, (conductor-GND)
≤ 85 V
Residual voltage with Ian (10/1000)µs (conductor-GND)
≤ 65 V
Response time tA (Core-Core)
≤ 1 ns (a-b)
Response time tA (Core-Earth)
≤ 100 ns (a, b)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
10 MHz (typical)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
2.5 MHz (typical)
Capacity (Core-Earth)
1.1 nF (1 MHz a-b)
Message: Surge protection fault
None
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) D1 (2.5 kA)
Connection data
Connection method
can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS
disconnect and switching strips
Connection type IN
COMTRAB plug-in system
Connection type OUT
COMTRAB plug-in system
Standards and Regulations
Standards/regulations
IEC 61643-21