Vision Akkus VISION SOLAR-AKKU 12 V, 36 AH 6FM36DX Ficha De Dados
Códigos do produto
6FM36DX
6FM36D
12V 36Ah(20hr)
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte
is absorbed by separators and plates and thus immobilized. Should the battery be
accidentally overcharged producing hydrogen and oxygen, special one-way valves allow the
gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is
completely sealed and is, therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component
Positive plate
Negative plate
Container Cover Safety valve
Terminal
Separator
Electrolyte
Raw material
Lead dioxide
Lead
ABS
ABS
Rubber
Pb
Fiberglass
Sulfuric acid
General Features
•
Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
•
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
•
UL-recognized component.
•
Can be mounted in any orientation.
•
Computer designed lead, calcium tin alloy
grid for high power density.
•
Long service life, float or cyclic
applications.
•
Maintenance-free operation.
•
Low self discharge.
Dimensions and Weight
Length(mm / inch)
195 / 7.68
Width(mm / inch)
130 / 5.12
Height(mm / inch)
155/ 6.10
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
10.2 / 22.5
Performance Characteristics
Nominal Voltage
12V
Number of cell
6
Design Life
10 years
Nominal Capacity 77
o
F(25
o
C)
20 hour rate (1.8A, 10.5V)
36Ah
10 hour rate (3.6A, 10.5V)
34Ah
5 hour rate (6.1A, 10.5V)
30.5Ah
1 hour rate (36A, 9.6V)
25Ah
Internal Resistance
Fully Charged battery 77
o
F(25
o
C)
10mOhms
Self-Discharge
3% of capacity declined per month at 20
o
C(average)
Operating Temperature Range
Discharge
-20~60
o
C
Charge
-10~60
o
C
Storage
-20~60
o
C
Max. Discharge Current 77
o
F(25
o
C)
330A(5s)
Short Circuit Current
850A
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C)
Cycle use
14.4-14.7V
Maximum charging current
9.9A
Temperature compensation
-30mV/
o
C
Standby use
13.6-13.8V
Temperature compensation
-20mV/
o
C
www.vision-batt.com
155 / 7.09
Cycle service life in relation to
depth of discharge
Number of cycles(cycles)
Capacity(%)
120
100
80
60
40
20
0
200 400 600 800 1000 1200 1400 1600
100% D.O.D.
50% D.O.D.
30% Depth of discharge