Lappkabel 4160509, Single Core Wiring Cable, , AWG, Orange Sheath 4160509 Ficha De Dados

Códigos do produto
4160509
Página de 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
 
 
Multi-Standard SC 2.1
 
 
DB 4160100                      
valid from:  2013-07-11
 
 
 
Originator:   KASC / PDC
 
approved:    HAPF / PDC 
Document: 
DB4160100EN 
page 1 of 1 
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.  
PD 0019/2.1_11.09EN 
Application 
 
These multi standard wiring cables SC2.1 are UL, CSA and HAR (VDE)* approved and are designed for use for control cabi-
net  wiring  as  well  as  for  installation  in  protective  tubes,  applicable  within  the  scope  of  the  UL-  or  Canadian  or  European 
standard specifications. They are especially qualified for wiring in industrial machines in accordance with NFPA 79. At room 
temperature they are widely resistant to oils. 
Application range:  
HAR: 
Wiring cable for internal wiring acc. to 
 
 
HD 516 S2 + A1 resp. DIN VDE 0298-300 
 
UL (AWM): 
oil resistant wiring cable for internal wiring 
 
UL (MTW):  
acc. to ANSI/NFPA 70 (National Electrical Code) 
 
CSA (TEW): 
oil resistant wiring cable for internal wiring of devices 
 
Design 
 
Design / Approvals  
H07V-K ◄HAR► (*) acc. to DIN EN 50525-2-31 / VDE 0285-525-2-31 
 
UL (AWM) Style 1015 acc. to UL 758 
 
UL (MTW) acc. to UL 1063, File-No. E198296 
 
CSA (TEW) acc. to C22.2 No. 217-09 
 
*For the dimensions 0.5; 0.75; 1.0 and16 mm² as well for the colours GN, YE, as for multi-coloured cores (except for GN YE) 
  there are no HAR-approval available (X07V-K)! 
 
Conductor 
fine-wired core of tinned copper strands acc. to IEC 60228 resp. VDE 0295, Class 5, 
 
UL 758 and CSA 22.2 
 
 
 
Core insulation 
special PVC-based compound 
 
 
Electrical properties 
 
Nominal voltage  
HAR H07V-K 
   
 
U
0
/U:    450 / 750 V AC 
 
UL (AWM) / UL (MTW) / CSA (TEW) 
U: 
600 V 
 
 
 
Test voltage  
2500 V AC 
 
 
 
 
 
Mechanical and thermal properties 
 
Min. bending radius  
fixed installation: 
OD≤8 mm: 
 
4 x OD** / 2 x OD*** 
 
 
8<OD≤12 mm:   
5 x OD** / 3 x OD*** 
 
 
OD>12 mm: 
 
6 x OD** / 4 x OD*** 
 
** at conventional usage; *** at cautious bending 
 
Temperature range 
fixed installation:   
HAR: 
 -40 °C up to  +70 °C max. conductor temp. 
 
 
UL (MTW): 
 -40 °C up to  +90 °C max. conductor temp. 
 
 
UL (AWM), CSA (TEW):  -40 °C up to +105 °C max. conductor temp. 
 
Flame resistance  
HAR:  
IEC 60332-1-2 resp. VDE 0482-332-1-2  
 
UL: 
VW-1 
 
CSA: 
FT1 
 
Oil resistance 
UL/CSA:  
60°C oil rating  
 
Tests                                 
acc. to IEC 60811 resp. VDE 0473 and VDE 0472, UL 1581 and CSA C22.2 
 
EC directive 
This cable is conform to EC-Directives 2006/95/EC (Low Voltage Directive) and  
 
2011 / 65 / EU (RoHS, Restriction of the use of certain hazardous substances).