Phoenix Contact Test disconnect terminal block USST 6-T 3070312 3070312 Ficha De Dados

Códigos do produto
3070312
Página de 16
Nov 10, 2013    2 / 16
Technical data
General
Checking the mechanical stability of terminal points (5 x
conductor connection)
Test passed
Bending test rotation speed
10 rpm
Bending test turns
135
Bending test conductor cross section/weight
0.2 mm² / 0.2 kg
Bending test conductor cross section/weight
6 mm
/ 1.4 kg
Bending test conductor cross section/weight
10 mm² / 2 kg
Bending test conductor cross section/weight
2.5 mm² / 0.7 kg
Result of bending test
Test passed
Conductor cross section tensile test
0.2 mm²
Tractive force setpoint
10 N
Conductor cross section tensile test
6 mm²
Tractive force setpoint
80 N
Conductor cross section tensile test
10 mm²
Tractive force setpoint
90 N
Conductor cross section tensile test
2.5 mm²
Tractive force setpoint
50 N
Tensile test result
Test passed
Tight fit on carrier
NS 35/NS 32
Setpoint
5 N
Result of tight fit test
Test passed
Requirements, voltage drop
≤ 3.2 mV
Result of voltage drop test
Test passed
Temperature-rise test
Test passed
Conductor cross section short circuit testing
6 mm²
Short-time current
0.72 A
Conductor cross section short circuit testing
10 mm²
Short-time current
1.2 kA
Short circuit stability result
Test passed
Proof of thermal characteristics (needle flame) effective
duration
30 s
Result of thermal test
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum
Service life test category 1, class B, body mounted
Test frequency
f
1
 = 5 Hz to f
2
 = 150 Hz
ASD level
0.02 g²/Hz
Acceleration
0.8 g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Oscillation, broadband noise test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine