Bender IR420-D4-2 B71016405 Ficha De Dados

Códigos do produto
B71016405
32
TDB101012en / Main catalogue part 1 – Insulation monitoring / 09.2011
Dipl.-Ing. W. Bender GmbH & Co. KG • Londorfer Str. 65 • 35305 Grünberg • Tel.: 06401 807-0 • Fax: 06401 807-259
Subject to change! – © Dipl.-Ing. W. Bender GmbH & Co. KG, Germany
1.1
A-ISOMETER® IR420
Insulation monitoring device
for unearthed AC control circuits (IT systems)
A-ISOMETER® IR420
Device features
• Insulation monitoring for
IT control circuits AC 0…300 V
• Two separately adjustable response values
•
Preset function
(automatic assignment of basic parameters)
(automatic assignment of basic parameters)
• Connection monitoring system/earth
• LEDs: Power On, Alarm 1, Alarm 2
• Internal/external test/reset button
• Two separate alarm relays
(one changeover contact each)
(one changeover contact each)
• N / O or N / C operation, selectable
• Fault memory behaviour, selectable
• Self monitoring with automatic alarm
• Multi-functional LC display
• Adjustable response delay
• Two-module enclosure (36 mm)
•
RoHS compliant
•
Push-wire terminal
(two terminals per connection)
(two terminals per connection)
Standards, approvals and certifications
Product description
The A-ISOMETER® IR420 monitors the insulation resistance of unearthed AC control circuits
(IT systems) 0…300 V. If the systems to be monitored include DC components, such as
switched-mode power supplies or solenoid valves, the display and operating characteristics
may be affected.
(IT systems) 0…300 V. If the systems to be monitored include DC components, such as
switched-mode power supplies or solenoid valves, the display and operating characteristics
may be affected.
The display and response values apply to pure AC systems.
An external supply voltage allows de-energised systems to be monitored too.
Application
• AC control circuits in the industrial sector, mechanical engineering, power plants, elevators,
automation systems etc.
• AC control and auxiliary circuits in accordance with IEC 60204-1: "Safety of machinery –
Electrical equipment of machines, Part 1: General requirements"
• Smaller AC IT systems such as lighting systems, mobile generators
Function
The currently measured insulation resistance is indicated on the LC display. In this way
any changes, for example when circuits are connected to the system, can be recognised
easily. When the value falls below the preset response values, the response delay "t
any changes, for example when circuits are connected to the system, can be recognised
easily. When the value falls below the preset response values, the response delay "t
on
"
starts. Once the response delay "t
on
" has elapsed, the alarm relays "K1 / K2" switch and
the alarm LEDs "AL1 / AL2" light up. Two separately adjustable response values/alarm relays
allow a distinction to be made between prewarning and alarm. If the insulation resistance
exceeds the release value (response value plus hysteresis), the alarm relays return to their
initial position. If the fault memory is enabled, the alarm relays remain in the alarm state
until the reset button is pressed or until the supply voltage is switched off. The device
function can be tested using the test button. The parameterisation of the device can be
carried out via the LC display or the function keys integrated in the front plate.
allow a distinction to be made between prewarning and alarm. If the insulation resistance
exceeds the release value (response value plus hysteresis), the alarm relays return to their
initial position. If the fault memory is enabled, the alarm relays remain in the alarm state
until the reset button is pressed or until the supply voltage is switched off. The device
function can be tested using the test button. The parameterisation of the device can be
carried out via the LC display or the function keys integrated in the front plate.
Connection monitoring
The connections to the system (L1 / L2) and earth (E / KE) are either automatically checked
every 24 h, or by pressing the test button or when supply voltage has been connected.
In case of interruption of a connecting lead, the alarm relay K2 switch, the LEDs
ON // AL1 // AL2 flash and the following message appears on the display:
every 24 h, or by pressing the test button or when supply voltage has been connected.
In case of interruption of a connecting lead, the alarm relay K2 switch, the LEDs
ON // AL1 // AL2 flash and the following message appears on the display:
"E.02" indicating a fault in the connecting leads to the system,
"E.01" signals a fault in the connecting leads to PE.
After eliminating the fault, the alarm relays return to their initial position either automatically
or by pressing the reset button.
or by pressing the reset button.
Preset function
After connecting the device for the first time, the nominal system voltage is measured
and the response values are set automatically.
and the response values are set automatically.
Measurement method
The A-ISOMETER® IR420 uses the measurement method "superimposed DC voltage".
Standards
The IR420 series complies with the requirements of the device standards: IEC 61557-8,
ASTM F1207M-96 (2007).
ASTM F1207M-96 (2007).