Security & Electronic Technologies GmbH
 
 
 
SECU-DATA  xxxM  and  also  SECU-DATA  xxxC  have  internal  block  termi-
nals  (type: WAGO  series  256,  ATEX  certified)  for  connection  of  the  corre-
sponding external wires.  
 
Important:  
Only  qualified  personnel  with  appropriate  training  and  authorisation  by  the 
installation manager is entitled to connect  SECU-DATA xxxx to an existing 
installation. Adhere to all applicable, local safety regulations. 
 
Important:  
Check carefully if either the SECU-DATA xxxM on the measurement site or 
the SECU-DATA xxxC on the controller location are operated in Ex-zone 1. 
If so, then an additional barrier SECU-BAR 125 has to be installed outside 
of  the  Ex-zone  1  between  the  not  intrinsically  safe  power  supply  and  the 
SECU-DATA xxxx to achieve the required level of ignition prevention.  
 
Hint: For SECU-DATA systems using the SECU-DATA 500C as a receiver 
the  function  of  the  relay  contacts  can  be  reconfigured  from  make  contacts 
to break contacts, see section Settings-SECU-DATA 500C relay configu-
ration
 on page 30. 
 
Attention: In  case of  connection problems  SECU-DATA  maintains the 
last valid information on the receiver output. This is valid for the cur-
rent output of SECU-DATA 42X/142X and also for the relay outputs of 
SECU-DATA  500C/1500C.  For  overfill  prevention  applications  with 
SECU-DATA 600M/710M it is important to ensure the turn-off of pumps 
in case of radio failures. This can be achieved by connection the make 
contact  of  Re1  of  the  SECU-DATA  500C/1500
C  in  series  to  the  “RF-
status” relay contact.