Secutech Radio modules ST002004 Ficha De Dados

Códigos do produto
ST002004
Página de 40
Page 34
 
Security & Electronic Technologies GmbH
 
 
 
 
Rated specification of SECU-DATA xxxx 
Supply voltage:  
11 V ... 40 V DC, 
intrinsically safe for applications in Ex-Zone 1 
Power consumption (without probe):  max. 1.2 W 
Ambient temperature:  -30°C 
≤ T
a
 
≤... +75°C  
 
ATEX - parameters for all SECU-DATA xxxx versions: 
Attention: For applications in explosive areas all inputs have to be 
connected to intrinsically safe lines only.
 
 
Power supply (pins 1-2, ignition protection: 
“ib”): 
U
= 25.2 V, I
= 131.3 mA, C
~ 0, L
~ 0 
 
RF-relay (pins (6-)7-8, ignition protection: 
“ib”): 
U
= 30 V, I
= 500 mA, C
~ 0, L
~ 0 
 
Technical specification of SECU-DATA 42xx  - 4-20 mA 
ATEX - parameters:  
SECU-DATA 420M/421M
–current input (pins 3-4, ign. protection: “ia”): 
U
= 25.2 V, I
= 146.8 mA, C
= 107 nF, L
= 2 mH 
SECU-DATA 420C/421C
–current output (pins 3-4, ign. protection: “ib”): 
U
= 30 V, I
= 150 mA, C
= 12 nF, L
~ 0 
 
Measurement uncertainty SECU-DATA 421M/421C - 16-Bit: 
Typical at 25°C:   
±0.02% of measured value 
Max. (-30°C 
… 75°C):  ±0.1% of measured value 
Resolution: 
 
0.4 µA 
Measurement uncertainty SECU-DATA 420M/420C - 12-Bit: 
Typical at 25°C:   
±0.1% of measured value 
Max. (-30°C 
… 75°C):  ±0.3% of measured value 
Resolution: 
 
6 µA 
Rise time: 
 
< 0.5 s 
 
Specification of SECU-DATA 500M/500C - Relay 
ATEX parameters :  
SECU-DATA 500M  
Relay inputs (pins 3-4, 5-6, ignition protection: 
“ib”): 
U
= 10 V, I
= 1 mA, C
= 1 µF, L
= ~ 0