Msf Vathauer Antriebstechnik GM 71/2 0.55 KW 20 100027 0006 Ficha De Dados

Códigos do produto
20 100027 0006
Página de 16
 
 
MSF-Vathauer Antriebstechnik GmbH & Co KG Am Hessentuch 6 – 8, D-32758 Detmold,  
Postfach 29 22, D -32719 Detmold 
Telefon: ++49 (0) 52 31/63 03-0 + 6 61 93, Telefax ++49 (0) 52 31/6 68 56 
E-Mail: Info@msf-technik.de, Internet: http://www.msf-technik.de 
Important for installations in wet internal conditions or outdoors 
 
Please note that trouble free operation can only be ensured if all the measures set 
out below are carried out. The motor terminal box is to be fitted so that the cable 
entries are directed downwards. Use suitable conduit screw fittings for the cable 
being used and if necessary use reducing nipples. Conduit screw fittings and plugs 
are to be coated with sealing compound, tightened up securely and recoated. 
Cableintakes are also to be made completely watertight. The sealing surfaces of 
terminal boxes and terminal box covers are to be properly cleaned before 
reassembly. Gaskets are to be glued down on one face. Brittle gaskets are to be 
replaced! When reassembling after maintenance work, etc. the end shield centering 
spigots are also to be coated with sealing compound. The corrosion protection 
consists of a number of paint coatings. Depending on environmental conditions the 
paint coating must be renewed on a regular basis or wherever necessary. The stated 
rated motor power applies for a maximum 40 °C ambient temperature and 
installation altitude up to1000 m (3330 feet) above sea level
.  
 
For higher ambient temperatures or installation at greater heights the power rating is 
reduced accordingly. (Refer to DIN 57530). The unimpeded access of ventilating 
cooling air must be ensured. Condensate water drain holes (only on customer's 
request) are plugged with plastic plugs that can be opened as required. Open 
condensate water drain holes are not permitted because then the enclosure IP44 
resp. IP55 is lost!