z
Press RUN Key. 7-segment Display will indicates 00.0to 05.0. Such value is the frequency
output value.
output value.
z Check the operation direction of the motor.
IF the direction of the motor is incorrect:
Press STOP Key, turn off the AC power supply. After Power indicator LED is off,
Press STOP Key, turn off the AC power supply. After Power indicator LED is off,
change over theT1 and T2.
Supply the power again, then check the motor direction.
z Press STOP key.
Step4 Check full speed at 50Hz/60Hz
z Change the frequency with ¿,À arrow mark , please press DATA/ENTER after setting
frequency.
z Set frequency to 50Hz/60Hz according to the above regulations.
z Press RUN Key, inspect the motor operation as motor accelerates to full load.
z Press STOP Key, inspect the motor operation as motor deceleration.
z Press RUN Key, inspect the motor operation as motor accelerates to full load.
z Press STOP Key, inspect the motor operation as motor deceleration.
Step5 Other settings
As for other function, please refer to 7300EV user manual.
Set acceleration time ………………………………… P. 4-9
Set deceleration time ………………………………… P. 4-9
Set upper frequency limit ….………………………... P. 4-12
Set lower frequency limit ……………………………. P. 4-12
Set motor rated current ………………………………P. 4-30
Set control mode (Vector, V/F) ………………………P. 4-26
Set acceleration time ………………………………… P. 4-9
Set deceleration time ………………………………… P. 4-9
Set upper frequency limit ….………………………... P. 4-12
Set lower frequency limit ……………………………. P. 4-12
Set motor rated current ………………………………P. 4-30
Set control mode (Vector, V/F) ………………………P. 4-26
Step6 vector Mode Settings
When the EV inverter is set to run in Vector Mode (C14=000), the motor parameters needs to
be set. The required in formation should be readily available on the nameplate of the motor.
(Motor kw=0.75 ¯ HP)
The parameters to set for vector operation ave:
Motor Rated Current (Amps) (F43) See page 4-23
Motor Rated Voltage (Volts) (F44) See page 4-23
Motor Rated Frequency (Hz) (F45) See page 4-23
Motor Rated Power (KW) (F46) See page 4-23
Motor Rated Speed (RPM) (F47) See page 4-23
Additional Vector Mode Settings to adjust for optimum operations are:
Torque boost gain (F48) See page 4-23
Slip compensation gain (F49) See page 4-24
Low Frequency Voltage Compensation (F50) See page 4-25
be set. The required in formation should be readily available on the nameplate of the motor.
(Motor kw=0.75 ¯ HP)
The parameters to set for vector operation ave:
Motor Rated Current (Amps) (F43) See page 4-23
Motor Rated Voltage (Volts) (F44) See page 4-23
Motor Rated Frequency (Hz) (F45) See page 4-23
Motor Rated Power (KW) (F46) See page 4-23
Motor Rated Speed (RPM) (F47) See page 4-23
Additional Vector Mode Settings to adjust for optimum operations are:
Torque boost gain (F48) See page 4-23
Slip compensation gain (F49) See page 4-24
Low Frequency Voltage Compensation (F50) See page 4-25