Technical data
Ambient conditions
Permissible humidity (storage/transport)
5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Weight
173 g
Note on weight specifications
With connector
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN 61000‑4‑2/IEC 61000‑4‑2 Criterion B; 6 kV
contact discharge, 8 kV air discharge
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2
Electromagnetic fields EN 61000‑4‑3/IEC 61000‑4‑3 Criterion A;
Field intensity: 10 V/m
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Fast
transients (burst) EN 61000‑4‑4/IEC 61000‑4‑4 Criterion B, 2 kV
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Transient
surge voltage (surge) EN 61000‑4‑5/IEC 61000‑4‑5 Criterion B;
DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical);
fieldbus cable shield: ±1 kV
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN 61000‑4‑6/IEC 61000‑4‑6 Criterion A; Test voltage
10 V
Conformance with EMC directives
Noise emission test according to EN 61000-6-3 Radio interference
properties EN 55022 Class B
Mechanical tests
Vibration resistance in acc. with EN  60068-2-6/IEC  60068-2-6 5 g
Mechanical tests
Shock in acc. with EN  60068-2-27/IEC  60068-2-27 25 g, 11 ms
period, half-sine shock pulse
Mechanical tests
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10
g
Interfaces
Fieldbus system
PROFINET
Name
PROFINET
Connection method
RJ45 socket, auto negotiation and autocrossing
Transmission speed
100 MBit/s (Full duplex)
Transmission physics
Ethernet in RJ45 twisted pair
Fieldbus system
Lokalbus
Name
Axioline F local bus
Connection method
Connection for bus base module
Transmission speed
100 MBit/s
Name
Service
Connection method
IFS-USB-PROG-ADAPTER
System limits of the bus coupler