Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 Ficha De Dados

Códigos do produto
6ED1057-3BA00-0AA8
Página de 344
LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
194
 
Manual, 06/2014, A5E33039675 
Timing diagram 
 
Functional description 
A 0 to 1 transition at input En saves the value of the signal at the analog input Ax. This saved 
process variable is referred to as "Aen". 
Both the analog actual values Ax and Aen are multiplied by the value at parameter A (gain), 
and parameter B (offset) is then added to the product:  
(Ax • gain) + offset = Actual value Aen, when input En changes from 0 to 1, or 
(Ax • gain) + offset = Actual value Ax. 
Output Q is set when the signal at input En = 1 and if the actual value at input Ax is out of 
range of Aen - Δ
 2
 to Aen + Δ
 1
 . 
Output Q is reset, when the actual value at input Ax lies within the range of Aen - Δ
 2
 to Aen+ 
Δ
 1
, or when the signal at input En changes to lo. 
Setting the Par parameter 
The gain and offset parameters are used to adapt the used sensors to the respective 
application. 
View in programming mode: 
 
View in parameter assignment mode (example):