Data Operations
2373_en_B
PHOENIX CONTACT
5-13
For example, given an input device on “A-00” that measures temperature in the range of 70
to 90° on a 0-10 Volt device, configure the the device as follows:
–
Set “Mode” to “Unipolar 0-10 Volts”
–
Set “Lower Value” to “70”
–
Set “Upper Value” to “90”
In this example, an input of 5 V would appear as a value of 80, while 0 V would be 70, and
10 V would be 90.
For more information on scaling and scaling examples, see Appendix C, “Technical
5.6
Using Analog Values in a Flow Chart
To use an analog value in a flowchart, follow these steps:
1.
Add an analog device to the nLC configuration (see “Configuring Analog I/O” on
2.
Provide scaling to the analog input if desired, by clicking the “Configure” button for the
expansion slot that has the analog I/O device.
3.
Open the Data Item Editor, and change the label name to a more fitting name for that
particular analog input.
4.
Use a Move block to move the analog input value to a register.
Figure 5-3
Use the “Move Block” dialog box to move analog input to a register
Once the analog value is in a register, treat it as any other integer value.