Wago 759-302 COMMISSIONING TOOL I/O-CHECK 2 759-302 Ficha De Dados

Códigos do produto
759-302
Página de 110
42      Controls (Overview) 
 
 
 Dialog 
Boxes 
 
 
  
WAGO-I/O-SYSTEM 
759 
  
WAGO-I/O-CHECK 
 
Warning! 
Outputs which are set manually by WAGO-I/O-CHECK (e.g. motor 
contactors, or valves) will remain until they are manually reset. In this 
case, switching the outputs off via control software (e.g. by limit switches) 
has no effect ! 
 
 
Note: 
Please refer to the chapter Notes on Setting and Resetting of Digital I/O 
Modules concerning the reaction of digital outputs in the different 
operation modes. 
 
 
Note: 
The state of digital outputs is indicated in the node display by colored 
LED´s. To toggle the state it is also possible to click the LED´s. 
A click with the right mouse key on the text box of the description column 
opens a context menu to rename the channel description. 
4.8.2.11  Context Menues of the Process Data Dialog Boxes of the Analog Input 
Modules 
A click with the right mouse key on the column header of the measuring 
values opens the following context menu: 
 
Hexadecimal 
This command switches the display format of the measuring 
value to a hexadecimal value. 
Units (V, mA, °C) 
This command switches the display format of the 
measuring value to physical units. 
State 
This command toggles an additional column with state 
values ON or OFF. 
The setting has effect on all measuring values of the analog input module. A 
click with the right mouse key on the measuring value itself opens the context 
menu to change the display format only for the selected measuring value. The 
menu item of the selected format is hooked. 
A click with the right mouse key on the column header of the state values 
opens the following context menu: