Controls (Overview) • 63
Dialog Boxes
WAGO-I/O-SYSTEM 759
WAGO-I/O-CHECK 2
Press the S
AVE
button to save the actual settings into a file. A dialog box will
be opened to enter a filename and path.
Press the O
PEN
button to open a file with already saved settings. A dialog box
will be opened to enter a filename and path.
4.8.3.2
2 Channel Input Module for RTDs 750-461/003-000 (Alignment Dialog
Box)
Box)
Use the edit boxes Offset and Gain to change the offset and gain values for
the hardware alignment. If required, you can adjust the offset for the wire
resistance with the edit box 2-Wire Offset when performing a 2-wire
measurement. Inputs are done in hexadecimal format.
the hardware alignment. If required, you can adjust the offset for the wire
resistance with the edit box 2-Wire Offset when performing a 2-wire
measurement. Inputs are done in hexadecimal format.
The output box shows the actual measurement value in hexadecimal format.
Press the OK button to store the changed values in the EEPROM of the
module and to close the alignment dialog box.
module and to close the alignment dialog box.
Press the C
ANCEL
button to quit the alignment dialog box without storing any
values inthe EEPROM of the module.
Closing the alignment dialog box switches the operation focus back to the
parameter dialog box.