Wago 759-302 COMMISSIONING TOOL I/O-CHECK 2 759-302 Ficha De Dados
![Wago](https://files.manualsbrain.com/attachments/a158027f97bd60ef35ba165ebe95b7eb4c48b423/common/fit/150/50/dc2120344b2d07e04a6f64f22734db497bf199abfea8b485bc6866bbcf91/brand_logo.png)
Códigos do produto
759-302
78 • Operation (Overview)
Change Parameters of the Selected I/O Module
WAGO-I/O-SYSTEM
759
WAGO-I/O-CHECK
2
5.7 Change Parameters of the Selected I/O Module
The following parameter changes are possible:
Analog I/O Modules
Setting and readjusting the input module for RTDs 750-461/003-000,
Setting the input module for thermocouples 750-469/003-000,
Special Modules
Setting the serial interface module RS 232 C 750-650/003-000,
Setting the serial interface module RS 485 750-653/003-000.
5.7.1 Setting RTD Module 750-461/003-000
Open the parameter dialog box of the selected bus module by executing the
command Settings in the context menu of the module in the node display or
navigationbar.
command Settings in the context menu of the module in the node display or
navigationbar.
Note:
Before changing the parameters make sure that you save the setted values
in a parameter file. This will enable you to access the original values in the
case of an incorrect parameterization. To do so, use the S
Before changing the parameters make sure that you save the setted values
in a parameter file. This will enable you to access the original values in the
case of an incorrect parameterization. To do so, use the S
AVE
and O
PEN
buttons in the parameter dialog box.
Select the connected sensor type and set the required operation parameters.
Press the D
EFAULT
button to show the default values for this module. You can
change the shown values if required.
Store the changed values in the EEPROM of the module by pressing the
A
A
PPLY
button and quit the parameter dialog box by pressing the C
LOSE
button.
Readjusting the RTD-module 750-461/003-000
A suitable calibration device (e.g. an electronic calibrator or highly accurate
precision resistors) is needed to adjust the module. The adjustment with two
resistors of 100Ohm and 200Ohm is described below. 100Ohm corresponds to
0°C and 200Ohm to 266.4°C according to DIN IEC 751.
precision resistors) is needed to adjust the module. The adjustment with two
resistors of 100Ohm and 200Ohm is described below. 100Ohm corresponds to
0°C and 200Ohm to 266.4°C according to DIN IEC 751.
Open the parameter dialog box of the selected bus module.
Set the module on Pt100 and 3-wire connection (RTD type = Pt100 and
connection = 3-wire) and switch off the user and WAGO scaling (user and
WAGO scaling = OFF). The temperature is emitted at intervals of 1/16°C.
Press the
connection = 3-wire) and switch off the user and WAGO scaling (user and
WAGO scaling = OFF). The temperature is emitted at intervals of 1/16°C.
Press the
ALIGNMENT
button to get to the alignment dialog box. First connect
the 100Ohm resistor and set the process value to 0x0000 (0°C) by modifying