Finder 80.91.0.240.0000 - 16A Monofunction Modular Timer SPDT-CO 400Vac IP20 80.91.0.240.0000 Ficha De Dados

Códigos do produto
80.91.0.240.0000
Página de 8
Functions
80 Series - Modular timers 6 - 8 - 16 A
(AI)
On-delay.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
(DI)
Interval.
Apply power to timer. Output contacts transfer immediately. 
After the preset time has elapsed, contacts reset.
(BE)
Off-delay with control signal.
Power is permenently applied to the timer.
The output contacts transfer immediately on closure of the
Signal Switch (S). Opening the Signal Switch initiates the
preset delay, after which time the output contacts reset.
(LI) 
Asymmetrical flasher (starting pulse on).
Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is
applied. The ON (T
1
) and OFF (T
2
) times are independently 
adjustable.
(LE) 
Asymmetrical flasher (starting pulse on) with control signal
Power is permenently applied to the timer.
Closing Signal Switch (S) causes the output contacts to
transfer immediately and cycle between ON (T
1
) and
OFF (T
2
), until opened.
Without control signal
With control signal
Without control signal
80.11/21/61
80.82
80.21
80.61
80.82
80.41
80.41
80.91
With control signal
80.91
(BI)
Power off-delay (True off-delay).
Apply power to timer (minimum 500ms). Output contacts
transfer immediately. Removal of power initiates the preset
delay, after which time the output contacts reset.
(SD) 
Star-delta.
Apply power to timer. The star contact (   ) closes immediately.
After preset delay has elapsed the star contact (   ) resets. 
After a further transfer time variable from (0.05…1)s the delta
contact ( Δ ) closes and remains in that position, until reset on
power off.
Wiring diagram
Type
80.11
80.91
• Possible to control an external load, such as another relay coil or timer, connected to the 
control signal
terminal B1.
* With DC supply, positive polarity has to be connected to B1 terminal (according to EN 60204-1).
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 230 V AC
B1 - A2  =  12 V DC
8